APS LSE-D16 Manual Download Page 5

 

Programming 

General 

Using the controls in programming mode: 

 

Icon

 

Description

 

Designation

 

Function in programming mode

 

 

Horn 
acknowledgement

 

HQ

 

Navigation up

 

 

Alarm acknowledge

 

LQ

 

Switch

 

 

Lamp test

 

LT

 

Navigation down

 

 

 

The programming mode is started as follows:  

Power  up  the  unit  and  push  the  HQ  and  LT  keys  at  the  same  time  within  10 
seconds.  If  no  other  keys  are  pressed  within  5  seconds,  LSE-D16  will  switch 
back to operating mode. If additional keys are pressed, the programming mode 
remains active for 30 seconds. If no other key is pressed for 30 seconds, LSE-
D16  will  return  to  operating  mode  and  will  take  over  the  programming.  The 
programming  mode  can  be  ended  by  pushing  the  HQ  and  LT  keys.  The 
settings  are  saved.  While  the  programming  mode  is  active,  the  power  LED 
blinks green. 

 
 
 

Programming levels 

 

LSE-D16 Operation-/Fault indicator has 6 programming levels: 

 

1. Inputs group 1 (red): Normally open / closed switchover 
2. Inputs group 1 (green): Normally open / closed switchover  
3. Virtual DIP switch: time delays and system settings 
4. Activation LT-Output as Common Output Priority 2 
5. RGB-Colour setting inputs group 1 
6. RGB-Colour setting inputs group 2 

 

Levels 4 to 6 are deactivated in the factory settings.  
They can be activated in level 3 with the virtual DIP switch 16. 

Summary of Contents for LSE-D16

Page 1: ...R UNIT LSE D16 24 AB MANUAL Safety regulations Mounting page 02 Schematics page 03 Control elements Technical data page 04 Programming page 05 Functionality page 09 Factory settings page 10 www aps sy...

Page 2: ...ply with the stipulations for safety extra low voltage SELV given in IEC 346 4 41 We recommend our power supplies of the EcoPower Series as they fulfil these stipulations completely Please note If the...

Page 3: ...ing a DC power supply The LT LQ and HQ functions can be customised see page 9 output functions The outputs are designed as a current sink and are not potential free If potential free contacts are requ...

Page 4: ...NC All inputs separate System inputs Buzzer HQ Lamp Lamp test LQ Lamp System outputs DC operation onl Buttons HQ LQ LT Optional output functions Common Common Priority 2 Output Control elements Horn...

Page 5: ...pressed for 30 seconds LSE D16 will return to operating mode and will take over the programming The programming mode can be ended by pushing the HQ and LT keys The settings are saved While the progra...

Page 6: ...to set if the inputs of group 1 are a NO closing contact or a NC opening contact The green flashing LED signals the selected fault indicator input The LQ key is used to switch the function Red LED of...

Page 7: ...ch on delay 2 On 3 Off Inner buzzer on 3 On Inner buzzer off 4 4 5 Off LQ output as the image of the LQ key active for 500 ms 5 On LQ output as collective indicator 6 Off According operation LED suppr...

Page 8: ...iority 2 Level 5 Signalisation Power LED blinking green LQ LED blinking yellow In level 5 the LED colour can be selected separately for each input of group 1 The inputs of group 1 light up in the prev...

Page 9: ...en LT button is pressed Common Output Prio 2 for inputs of group 1 Level 3 DIP 16 Level 4 9 HQ Output active for 500ms when LT button is pressed 10 LQ Output active for 500ms when LT button is pressed...

Page 10: ...evel 5 LED Colour for all inputs of group 1 red Level 6 LED Colour for all inputs of group 2 green Reset to factory settings The factory settings can be restored by pressing the three buttons HQ LQ LT...

Reviews: