Frequency
Display
Output Voltage Below Limit.
If the output voltage is lower than the voltage setting by
more than 5V on the 0-150V range or 10V on the 0-300V range, the FREQUENCY display
will show LVP (Underr Voltage Protect); an alarm will sound; the OUTPUT/RESET LED
will flash; and the VOLTAGE and CURRENT displays will show the corresponding values
at the time of under-voltage.
Frequency
Display
Output Power Limit Exceeded.
If the output power exceeds 125% of the rated output
for 0.3 seconds or 110% of the rated output for 1.0 seconds the FREQUENCY display will
show OPP (Over Power Protect); an alarm will sound; the OUTPUT/RESET LED will flash;
and the VOLTAGE and CURRENT displays will show the corresponding values at the time
of over-power.