SETUP & TESTING

SETUP & TESTING

The following tables contain the Indoor Air Quality system settings and their details . Default settings are shown in 

bold

 . Some settings are only present dependent upon the value of other settings .

The use of an outdoor temperature sensor (recommended) enables additional Indoor Air Quality functionality . If the 
outdoor temperature sensor was not enabled in the HVAC system settings, HVAC system setting 15, Outdoor Sensor, 
will be presented prior to entering the Indoor Air Quality system settings .
Please refer to the Model 8910W Owner’s Manual for further information about thermostat features . 

Air Cleaning System Settings Table

System setting

Description

Factory default setting (bold)  

and setting range

Air Cleaner Installed

Selects if an air cleaner is installed . (If set to No, no other 

air cleaning settings will be available .)

No

Yes

Change Air Filter Reminder

The period for displaying the “Change Air Filter” message . 

Off

1 to 12 months or “Off” to disable

 

Humidifier System Settings Table

System setting

Description

Factory default setting (bold)  

and setting range

Humidifier Installed

Selects if a humidifier is installed . 

Yes/On HVAC

 is used 

for applications where the humidifier is installed on the 

HVAC duct . 

Yes/Standalone

 is used for application where 

the humidifier is independent of the HVAC system . (If set to 

no, no other humidifier settings will be available .)

No

Yes/On HVAC

Yes/Standalone

Humidifier Mode

Selects auto or manual mode . Auto mode controls humidity 

based on the humidity setting and outdoor temperature . 

Manual mode controls humidity based on the %RH setpoint . 

(Auto mode is only available if outdoor sensor is set to 

Installed .)

Auto

Manual

Humidity Setpoint 

Deadband

Selects the minimum difference between the humidifier 

and dehumidifier setpoints . (Only available if a humidifier is 

installed and dehumidifier control is set to air conditioner . 

Available in both set-ups .)

10 Percent RH

10 to 20 Percent RH

Humidifier Operation

Selects when humidification is allowed to occur relative 

to heating and fan operation . Without Fan allows 

humidification to occur without the HVAC fan . This option 

should only be used when the humidifier is independent 

of the HVAC system . Note: 

Without Fan

 is only available 

when 

Humidifier Installed

 is set to 

Yes/Standalone

 .

Heat Only

Heat or Fan

Forces Fan

Without Fan

 CAUTION:

 When 

Humidifier Operation

 is set to 

Without Fan

 the thermostat will turn on humidification 

without energizing the HVAC fan . Do not select this option when the humidifier is installed on the HVAC duct . 

Without airflow moisture can accumulate in the duct resulting in significant damage .

Change Water Panel 

Reminder

Selects the when the “Change Water Panel” message is 

displayed .

Off

1 Per Season

2 Per Season

300 Hours

600 Hours

INDOOR AIR QUALITY SYSTEM SETTINGS TABLES

Dehumidifier System Settings Table

System setting

Description

Factory default setting (bold)  

and setting range

Dehumidifier Control

Selects method of dehumidification . (If set to None, no 

other dehumidifier settings will be available .)

None

 (no dehumidification installed)

Whole Home

Air Conditioner

Humidity Setpoint Deadband

Select the minimum difference between the humidifier 

and dehumidifier setpoints . (Only available if both a 

humidifier and dehumidifier are installed . Available in 

both set-ups .) 

10 Percent RH

10 to 20 Percent RH

Lockout Dehumidifier During 

Cooling 

Selects if dehumidification is disabled during a cooling 

call .

No

Yes

Dehumidifier Forces Fan

Select if dehumidification can turn on the fan .

No

Yes

Dehumidifier Service 

Reminder

The period for displaying the “Dehum Service 

Reminder” message .

Off

1 to 12 months or “Off” to disable

Dehumidifier Overcooling 

Limit

Selects the amount of overcooling that can occur 

for dehumidification . (Only available if Dehumidifier 

Control is set to Air Conditioner .)

3°F (1.5°C)

1°F to 3°F (0 .5°C to 1 .5°C) 

Dehumidify in Vacation 

Mode

Selects if dehumidification with the air conditioner is 

done in Vacation Mode . (Only available if Dehumidifier 

Control is set to Air Conditioner .)

No

Yes

Vacation Dehumidifier Low 

Temp Limit

Sets the lowest temperature the air conditioner 

will cool to, to meet RH setpoint in Vacation Mode . 

(Only available if Dehumidifier Control is set to Air 

Conditioner .)

75°F (23.5°C)

70°F to 85°F (21°C to 28 .5°C)

Note:

 Refer to manuals for humidifier, dehumidifier, air cleaner, and ventilation products for recommended 

installation and operation .

System setting

Description

Factory default setting (bold)  

and setting range

Reminder Month (Change 

Water Panel Reminder set 

to 1 Per Season) 

First Reminder Month 

(Change Water Panel 

Reminder set to 2 Per 

Season)

Change Water Panel Reminder set to 1 Per Season: 

Determines the month the “Change Water Panel” message 

is displayed . 

Change Water Panel Reminder set to 2 Per Season: 

Determines the first month the “Change Water Panel” 

message is displayed .

October

November

December

January

February

March

April

May

June

July

August

September

Second Reminder Start 

Month

Determines the second month the “Change Water Panel” 

message is displayed . (Only available when Change Water 

Panel Reminder set to 2 Per Season .)

October

November

December

January

February

March

April

May

June

July

August

September

English

 15

14 

English

Summary of Contents for 8910W

Page 1: ...stem settings table 12 13 Indoor Air Quality system settings tables 14 16 Air cleaning system settings table 14 Humidifier system settings table 14 15 Dehumidifier system settings table 15 Ventilation system settings table 16 System test menu 17 18 System test tables 18 20 Quick reference to controls display 21 22 Troubleshooting 22 23 Error codes 23 Thermostat features 23 Specifications 24 HVAC W...

Page 2: ...CONTROL MODULE MOUNTING 1 Remove the rear mounting plate from the thermostat 2 Pull wires through the opening on the rear mounting plate 3 Position and level the mounting plate of the thermostat on wall and mark the hole locations with a pencil 4 Drill 1 4 holes and insert supplied anchors drywall only 5 Place mounting plate over anchors insert and tighten screws 6 Seal wire entry holes to prevent...

Page 3: ...2 sensor to the ODT terminals and enabling the outdoor sensor in the installer set up menu When an outdoor sensor is installed the features below will be enabled In heat pump mode the outdoor temperature sensor can be used to efficiently utilize an air source heat pump When the outdoor temperature is less than the Low Balance Point the heat pump will be locked out and only auxiliary heating will b...

Page 4: ...OLING LOCATE SENSOR IN SHADED AREA CONVENTIONAL HEAT COOL TWO TRANSFORMER REMOVE JUMPER HEATING TRANSFORMER COOLING TRANSFORMER C R W W2 B Y Y2 O G L RH RC C 3 EQ HP HC G Y3 Y2 Y W3 W2 W TRANSFORMER THERMOSTAT 1 2 2nd COOLING 1st COOLING FAN 1st HEATING 2nd HEATING 3rd HEATING 3rd COOLING 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source 1 RE...

Page 5: ...FAULT DETECT REVERSING VALVE REVERSING VALVE 2nd HEATING 1st HEATING FAN 1st COMPRESSOR 2nd COMPRESSOR 2 1 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source INDOOR AIR QUALITY WIRING DIAGRAMS INDOOR AIR QUALITY WIRING WITH SEPARATE TRANSFORMERS INDOOR AIR QUALITY WIRING WITH A SINGLE TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER VNT DH HUM ...

Page 6: ... adjust the setting Press DONE to save and exit or CANCEL to exit without saving The thermostat will discard changes and exit if nothing is pressed within 60 seconds To reset the installer settings to the default reset the thermostat by pressing the RESET button for 5 seconds SETTING NUMBER SETTING DESCRIPTION SETTING OPTIONS EQUIPMENT TYPE SELECTION SWITCH SW1 This thermostat has the option of be...

Page 7: ... SETUP TESTING SETUP TESTING HVAC INSTALLER SYSTEM SETTINGS TABLE CONTINUED The following table contains the system settings and their details Default settings are shown in bold Some settings are only available dependent upon the value of other settings HVAC INSTALLER SYSTEM SETTINGS TABLE System setting Description Factory default setting bold and setting range 01 Equipment Type Equipment type se...

Page 8: ...umidifier is installed on the HVAC duct Without airflow moisture can accumulate in the duct resulting in significant damage Change Water Panel Reminder Selects the when the Change Water Panel message is displayed Off 1 Per Season 2 Per Season 300 Hours 600 Hours INDOOR AIR QUALITY SYSTEM SETTINGS TABLES Dehumidifier System Settings Table System setting Description Factory default setting bold and ...

Page 9: ...imit Sets low ventilation temperature lockout limit Only available if Enable Low Vent Temperature Limit is set to Yes 10 F 12 C 10 F to 40 F 24 C to 6 C HVAC Fan with Vent Selects if ventilation forces the fan on Yes with high and low limits is only available if Outdoor Sensor is set to Installed Yes Yes with high and low limits No Enable High Mixing Temperature Enables high mixing temperature Onl...

Page 10: ...Heat Compressor Stages Aux Stages W W2 B Y Y2 O G 1 1 1st Stage Test ON ON ON 1 1 2nd Stage Test ON ON ON ON 2 1 1st Stage Test ON ON ON 2 1 2nd Stage Test ON ON ON ON 2 1 3rd Stage Test ON ON ON ON ON 1 2 1st Stage Test ON ON ON 1 2 2nd Stage Test ON ON ON ON 1 2 3rd Stage Test ON ON ON ON ON 2 2 1st Stage Test ON ON ON 2 2 2nd Stage Test ON ON ON ON 2 2 3rd Stage Test ON ON ON ON ON 2 2 4th Stag...

Page 11: ...MATICALLY TURNS OFF FAN MODE BUTTON FAN MODE SETTING SYSTEM MODE BUTTON SYSTEM MODE SETTING WI FI SIGNAL STRENGTH CURRENT TIME DATE MAIN MENU BUTTON HEAT BLAST BUTTON TEMPERATURE ADJUSTMENT AIR CLEANING BUTTON ENTERS EVENT BASED AIR CLEANING CONTROL SCREEN HUMIDITY CONTROL BUTTON ENTERS HUMIDITY CONTROL SCREEN FRESH AIR BUTTON ENTERS VENTILATION CONTROL SCREEN HOLD BUTTON SETS OR CLEARS HOLD HEAT ...

Page 12: ...s connected to the proper terminal O is active in cooling and B is active in heating HEAT COOL BOTH ON AT SAME TIME EQUIPMENT CONTROL MODULE LEDs Check SW1 Equipment Type to make sure it is set to match the installed heating cooling equipment Check to make sure heating and cooling wires are not shorted together HEATING EQUIPMENT IS RUNNING IN COOL MODE Check SW1 Equipment Type to make sure it is s...

Page 13: ... to 50 R H Dehumidification 40 to 90 R H SPECIFICATIONS Electrical Operating voltage 24VAC 18 30VAC Current Maximum 2 5A total 1 0A single output Maximum surge current 5A Environment Temperature Shipping 30 to 150 F 34 to 65 C Temperature Thermostat Operating 32 to 120 F 0 to 48 C Temperature Equipment Control Module Operating 32 to 158 F 0 to 70 C Relative humidity Operating 5 to 90 R H non conde...

Page 14: ...ire interior 14 16 Tabla de configuración del sistema de purificación de aire 14 Tabla de configuración del sistema del humidificador 14 15 Tabla de configuración del sistema del deshumidificador 15 Tabla de configuración del sistema de ventilación 16 Menú de prueba del sistema 17 18 Tablas de prueba del sistema 18 20 Referencia rápida sobre los controles y la pantalla 21 22 Solución de problemas ...

Page 15: ...to 2 Tire de los cables a través de la abertura de la parte posterior de la placa de montaje 3 Coloque y nivele la placa de montaje del termostato en la pared y utilice un lápiz para marcar las ubicaciones de los orificios 4 Realice orificios de 1 4 in y coloque los anclajes que se proporcionan solo para panel de yeso 5 Coloque la placa de montaje sobre los anclajes inserte y ajuste los tornillos ...

Page 16: ... al habilitar el sensor exterior desde el menú de configuración del instalador Si se instala un sensor exterior se activarán las funciones mencionadas a continuación En el modo de bomba de calor se puede utilizar el sensor de temperatura exterior para utilizar de forma eficiente una bomba de calor de fuente de aire Cuando la temperatura exterior es menor que el Low Balance Point punto de equilibri...

Page 17: ... Ï1 7 3 Ï1 7 3 1 5 0 172 7 3 COLOQUE EL SENSOR EN EL ÁREA SOMBREADA SISTEMA DE CALOR FRÍO CON DOS TRANSFORMADORES CONVENCIONALES RETIRAR PUENTE DE CONEXIÓN TRANSFORMADOR DE LA CALEFACCIÓN TRANSFORMADOR DEL SISTEMA DE ENFRIAMIENTO 5 2 5 5 4 3 TRANSFORMADOR 7 50267 72 1 5 0 172 7 3 1 5 0 172 7 3 9 17 25 Ï1 7 3 Ï1 7 3 Ï1 7 3 1 5 0 172 7 3 R y C pueden recibir alimentación desde el transformador del e...

Page 18: ...N 7 7 5 9È 98 19 56 Ï1 9È 98 19 56 Ï1 2035 625 7 3 2035 625 7 3 9 17 25 Ï1 7 3 Ï1 7 3 R y C pueden recibir alimentación desde el transformador del equipo de HVAC o desde cualquier otra fuente de 24 VCA que reciba energía constantemente DIAGRAMAS DE CABLEADO DEL SISTEMA DE CALIDAD DEL AIRE INTERIOR CABLEADO DEL SISTEMA DE CALIDAD DEL AIRE INTERIOR CON TRANSFORMADORES INDIVIDUALES CABLEADO DEL SISTE...

Page 19: ...Ahora se pueden modificar las configuraciones del sistema Presione NEXT Siguiente o BACK Atrás para revisar las configuraciones Presione o para ajustar la configuración Presione DONE Listo para guardar y salir o CANCEL Cancelar para salir sin guardar los cambios Si no se presiona nada en 60 segundos el termostato descartará los cambios y saldrá de la pantalla Para restablecer la configuración del ...

Page 20: ...e la configuración del sistema y detalles de la configuración La configuración predeterminada se muestra en negrita Algunas opciones de configuración están disponibles según el valor de otras opciones TABLA DE CONFIGURACIÓN DEL SISTEMA DEL INSTALADOR DE HVAC Configuración del sistema Descripción Configuración por defecto de fábrica negrita y rango de configuración 01 Equipment Type Tipo de equipo ...

Page 21: ...mular humedad en el conducto y como resultado provocador daños importantes Change Water Panel Reminder Aviso de cambio del panel de agua Seleccione esta opción cuando aparece el mensaje Change Water Panel Cambiar panel de agua Apagado 1 por temporada 2 por temporada 300 horas 600 horas TABLAS DE CONFIGURACIÓN DEL SISTEMA DE CALIDAD DEL AIRE INTERIOR Tabla de configuración del sistema del deshumidi...

Page 22: ...ent Temperature Limit Habilitar límite inferior de la temperatura de ventilación Permite habilitar el límite inferior de bloqueo de la temperatura del sistema de ventilación Solo estará disponible si la opción Outdoor Sensor Sensor exterior se establece en Installed Instalado No Sí Low Vent Temperature Limit Límite inferior de la temperatura de ventilación Permite establecer el límite inferior de ...

Page 23: ...O ENCENDIDO 2 1 Prueba de 2 º etapa ENCENDIDO ENCENDIDO ENCENDIDO ENCENDIDO 2 1 Prueba de 3 º etapa ENCENDIDO ENCENDIDO ENCENDIDO ENCENDIDO ENCENDIDO 1 2 Prueba de 1 º etapa ENCENDIDO ENCENDIDO ENCENDIDO 1 2 Prueba de 2 º etapa ENCENDIDO ENCENDIDO ENCENDIDO ENCENDIDO 1 2 Prueba de 3 º etapa ENCENDIDO ENCENDIDO ENCENDIDO ENCENDIDO ENCENDIDO 2 2 Prueba de 1 º etapa ENCENDIDO ENCENDIDO ENCENDIDO 2 2 ...

Page 24: ... APAGA DE MANERA AUTOMÁTICA BOTÓN DEL MODO VENTILADOR CONFIGURACIÓN DEL MODO VENTILADOR BOTÓN DEL MODO SISTEMA CONFIGURACIÓN DEL MODO SISTEMA INTENSIDAD DE LA SEÑAL DE WI FI HORA Y FECHA ACTUAL BOTÓN DEL MENÚ PRINCIPAL BOTÓN DEL MODO RÁFAGA DE CALOR AJUSTE DE LA TEMPERATURA BOTÓN DEL SISTEMA DE PURIFICACIÓN DE AIRE INGRESA A LA PANTALLA DE CONTROL DEL SISTEMA DE PURIFICACIÓN DE AIRE EVENT BASED BO...

Page 25: ... modo calefacción LAS OPCIONES CALOR FRÍO ESTÁN ENCENDIDAS AL MISMO TIEMPO LUCES LED DEL MÓDULO DE CONTROL DEL EQUIPO Verifique la función SW1 Equipment Type Tipo de equipo para asegurarse de que esté configurada de modo que coincida con el equipo del sistema de calefacción y enfriamiento instalado Verifique que los cables del sistema de calefacción y enfriamiento no estén en cortocircuito EL EQUI...

Page 26: ...cación de 10 a 50 de R H Deshumidificación de 40 a 90 de R H ESPECIFICACIONES Información eléctrica Voltaje de funcionamiento 24 VCA de 18 a 30 VCA Corriente Máxima 2 5 A total 1 0 A salida única Sobrecorriente máxima 5 A Ambiente Temperatura de envío De 30 a 150 F de 34 a 65 C Temperatura del termostato en funcionamiento De 32 a 120 F de 0 a 48 C Temperatura del módulo de control del equipo en fu...