SETUP & TESTING
Ventilation System Settings Table
System setting
Description
Factory default setting (bold)
and setting range
Fresh Air Vent Installed
Selects if ventilation is installed . (If set to No, no other
ventilation settings will be available .)
No
Yes
Fresh Air Setup Type
Selects if ventilation is configured through the Code setup
or Comfort . Comfort setup has more lockout options . Code
setting ensures missed lockout time is made up .
Comfort
Code
Number of Bedrooms
Selects the number of bedrooms to be used for the Calculated
Minutes per Hour .
3 Bedrooms
1 to 10 Bedrooms
Home Size
Selects the size of the home to be used for the Calculated
Minutes per Hour .
2500 SQ FT
500 to 7500 SQ FT
Measured CFM
Selects the ventilation CFM to be used for the Calculated
Minutes per Hour .
110 CFM
30 to 250 CFM
Calculated Minutes
per Hour
Displays the Fresh Air Time calculated .
None
Range 6 to 60 Minutes
Override
Manual adjustment of Calculated Minutes per Hour .
(Calculated Minutes per Hour)
Range 6 to 60 Minutes
Enable High Vent RH
Limit
Selects if ventilation is disabled if the indoor RH exceeds the
indoor RH limit . (Only available if Fresh Air Setup is set to
Comfort .)
Yes
No
High Vent RH Limit
Sets the ventilation indoor RH lockout limit . (Only available if
Enable High Vent RH Limit is set to Yes .)
55%
45% to 70%
Enable Low Vent RH
Limit
Selects if ventilation is disabled if the indoor RH exceeds the
indoor RH limit . (Only available if Fresh Air Setup is set to
Comfort .)
No
Yes
Low Vent RH Limit
Sets the ventilation indoor RH lockout limit . (Only available if
Enable Low Vent RH Limit is set to Yes .)
20%
10% to 30%
Enable High Vent
Temperature Limit
Enables high ventilation temperature lockout limit . (Only
available if Outdoor Sensor is set to Installed .)
No
Yes
High Vent Temperature
Limit
Sets high ventilation temperature lockout limit . (Only available
if Enable High Vent Temperature Limit is set to Yes .)
100°F (38°C)
85°F to 105°F (29°C to 41°C)
Enable Low Vent
Temperature Limit
Enables low ventilation temperature lockout limit . (Only
available if Outdoor Sensor is set to Installed .)
No
Yes
Low Vent Temperature
Limit
Sets low ventilation temperature lockout limit . (Only available
if Enable Low Vent Temperature Limit is set to Yes .)
10°F (-12°C)
-10°F to 40°F (-24°C to 6°C)
HVAC Fan with Vent
Selects if ventilation forces the fan on . (Yes with high and low
limits is only available if Outdoor Sensor is set to Installed .)
Yes
Yes with high and low limits
No
Enable High Mixing
Temperature
Enables high mixing temperature . (Only available is HVAC Fan
with Vent is set to Yes with high and low limits .)
No
Yes
High Mixing
Temperature
Sets the high mixing temperature . (Only available if Enable
High Mixing Temperature is set to Yes .)
80°F or (26°C)
60°F to 105°F (14°C to 41°C)
Enable Low Mixing
Temperature
Enables low mixing temperature . (Only available is HVAC Fan
with Vent is set to Yes with high and low limits .)
No
Yes
Low Mixing
Temperature
Sets the Low mixing temperature . (Only available if Enable
Low Mixing Temperature is set to Yes .)
40°F (6°C)
0°F to 50°F (-18°C to 12°C)
Fresh Air Service
Reminder
The period for displaying the “SERVICE FRESH AIR” message .
OFF
1 to 12 months or “OFF” to disable
SETUP & TESTING
SYSTEM TEST MENU
The system test menu is used to test a system after installation . The outputs of the thermostat can be manually
activated to test their function . The instructions below show how to enter the test mode and turn outputs on and off .
Each equipment test will begin with the selection of turning on the output or stage as shown below .
Press
or
to change the selection .
Press
[NEXT]
to accept the selection and proceed to the next step .
If
YES
is selected, the thermostat will test the corresponding output . If
NO
is selected, the thermostat will proceed
to the next step .
SYSTEM TEST STEPS
Heating equipment test
Cooling equipment test
Fan equipment test
Humidification equipment test
Dehumidification equipment test
Ventilation equipment test
Air Cleaning equipment test
HOW TO ENTER THE SYSTEM TEST MENU:
Press [MODE]
to set system to off .
Press and hold [FAN]
and
[MODE]
for three seconds
to enter system test mode .
The first screen of the installer test displays the
equipment configuration .
Press [NEXT]
to enter the first installation test or
[CANCEL]
to exit .
TEMPERATURE
TEMPERATURE
EQUIPMENT TEST
SELECTION
HUMIDITY
HUMIDITY
OUTDOOR
TEMPERATURE
OUTDOOR
TEMPERATURE
EQUIPMENT
CONFIGURATION
TEST TO BE RUN
English
17
16
English