- 30 -
1. DIFFERENTIAL
Determines the temperature above/below the temperature
setting at which the heating or cooling equipment will turn
on. For example, a heat temperature setting of 70°F with a
differential of 2° will result in the equipment turning on and
off to maintain the temperature between 68°F and 70°F. If the
second stage differential is also 2°, the second stage would
be used to ensure the temperature did not drop below 66°.
However, once the second stage is turned on, it will stay on
until the temperature again reaches the 70° setting. The default
setting for the first stage and second stage differential is 1°.
To change the differential settings:
1. Make sure the thermostat is in the OFF mode.
2. Press and hold both the
and
buttons for 3 seconds.
– The display will show the ADV. SETTINGS MENU.
3. Use the
or
button to highlight “SET DIFFERENTIAL”
and press the SELECT button.
– If the thermostat SINGLE/MULTI dip switch is set for
MULTI, two differentials will appear, if set for SINGLE,
only one will appear.
4.
To cancel
, press the BACK button. This will return you
to the ADV. SETTINGS MENU.
5.
To change
the first stage differential, press the
and
button to raise or lower the setting. To change the second
stage differential, press the SELECT button.
6.
To finish
and return to the ADV. SETTINGS MENU, press
the SELECT button after the value(s) have been set.
–
For heat pumps
– the auxiliary heat differential is the
same as the first stage differential in single-stage heat
pump applications and is the same as the second stage
differential for two-stage heat pump applications.
(10) CUSTOMIZE THE APPLICATION SETTINGS
Summary of Contents for 8570
Page 13: ... 9 Diagram 1 Single Stage Furnace and AC ...
Page 14: ... 10 Diagram 2 Two Stage Furnace and AC ...
Page 15: ... 11 Diagram 3 Two Stage Roof Top Unit ...
Page 16: ... 12 Diagram 4 Boiler with AC ...
Page 17: ... 13 Diagram 5 Radiant Floor 1st Stage Heat with Furnace 2nd Stage Heat and AC ...
Page 18: ... 14 Diagram 6 Single Stage Heat Pump ...
Page 19: ... 15 Diagram 7 Two Stage Heat Pump ...
Page 22: ...CIR GND IDS ODT ZA ZB C Figure 7 18 ...
Page 26: ... 22 CIR GND IDS ODT ZA ZB C Figure 9 ...
Page 40: ...DP 10006198 01 05 B2203358B Printed in U S A P O BOX 1467 MADISON WI 53701 1467 ...