- 28 -
7. CHECK COOLING OPERATION
Notes:
1. To avoid the minimum off times during system
checkout, always start the check out procedure
in the OFF mode.
2. Do not operate air conditioning at low outdoor
temperatures. Refer to equipment manufacturer’s
recommendations for safe operating temperatures.
• Set the thermostat to the OFF mode.
• Set the thermostat to the COOL mode:
– The O terminal will energize when in the Cool mode.
• Lower the cool setting to 5° below the room temperature
to initiate a 1st stage cool call. The mode display will
change from “COOL MODE” to “COOLING”, which will flash
when the thermostat is calling for cooling:
– Y1 and G terminals will energize.
• Wait 4-minutes for 2nd Stage:
– Y1, Y2 and G terminals will energize.
• Set the thermostat to the OFF mode.
Symptom
Cause
Thermostat does not call for cooling
Minimum-off times. Change the mode to OFF first, then change the mode
to COOL and make a call for cooling.
Cooling does not come on at all
RC terminal not connected – see wiring diagrams.
Cooling equipment power not on.
Heat comes on instead of cooling
Reversing valve wiring.
Miswiring – check wire colors at thermostat and HVAC equipment.
TROUBLESHOOTING – COOLING OPERATION
Summary of Contents for 8570
Page 13: ... 9 Diagram 1 Single Stage Furnace and AC ...
Page 14: ... 10 Diagram 2 Two Stage Furnace and AC ...
Page 15: ... 11 Diagram 3 Two Stage Roof Top Unit ...
Page 16: ... 12 Diagram 4 Boiler with AC ...
Page 17: ... 13 Diagram 5 Radiant Floor 1st Stage Heat with Furnace 2nd Stage Heat and AC ...
Page 18: ... 14 Diagram 6 Single Stage Heat Pump ...
Page 19: ... 15 Diagram 7 Two Stage Heat Pump ...
Page 22: ...CIR GND IDS ODT ZA ZB C Figure 7 18 ...
Page 26: ... 22 CIR GND IDS ODT ZA ZB C Figure 9 ...
Page 40: ...DP 10006198 01 05 B2203358B Printed in U S A P O BOX 1467 MADISON WI 53701 1467 ...