20
2.9 Boost time:
Available for System 1 only
This option will display only if the
Boost
setting is chosen for
Pump P2
on the
Service
menu /
Pump P2
(See Section
1.15
).
- Highlight
P2 Boost time
and press
(>)
- Use the
(+)
or
(-)
buttons to set the duration for the running time of P2
(Adjustable from 1 to 10 minutes with factory default set at 5 minutes)
2.10 Mintemp Collector
:
This option allows you to set the minimum collector temperature required for solar loading.
(Adjustable from -9°F to 210°F with factory default set at -9°F)
Settings
--------------
Maxtemp tank2
149°F
dTMax tank2
49°F
dT Min tank2
38°F
Min rev pump
100%
Mintemp prio
85°F
Mintemp coll. 32°F
Settings
--------------
dT Max tank1
49°F
dT Min tank1
38°F
Maxtemp tank2
149°F
dT Max tank2
49°F
dT Min tank2
38°F
Min rev pump
100%
P2 Boost time 5min
Tank1
T2
(°F)
dTMin
dTMax
P1
Main
pump
Collector
T1
(°F)
Maxtemp
Tank1
dTMax
dT = T1 – T2
100%
0%
dTMax
Boost time
(P2 running time)
P2
Booster
pump