
5
SECTION 5 INSTALLATION
5.1
PHYSICAL LOCATION:
Charging areas should be clean and dry. The temperature of the charging room should be
between 32
o
F (0
o
C) and 104
o
F (40
o
C). Combustible materials, open flames and smoking must
not be permitted in or near the charging area. It is very important to keep all four sides,
including the fans, free from obstructions; there should be at least 2 feet between the charger
front or sides and any other object.
5.2
MOUNTING:
The Maverick charger cabinets must be mounted on a surface constructed from
non-combustible material, such as stone, brick, concrete or metal. Mounting holes are provided
in the frame for securing the charger. Do not use the charger while it is attached to the pallet.
5.3
INPUT POWER CONNECTION:
The Maverick chargers are shipped from the factory connected for 480VAC, 3 Phase.
WARNING
VERIFY THE AC ELECTRICAL SERVICE IS DISCONNECTED AT THE SOURCE
BEFORE ATTEMPTING TO CONNECT AC POWER TO THE CHARGER.
CAUTION
To reduce the risk of fire, use only on circuits provided with branch circuit protection
indicated in Table 5.3.1 in accordance with the NATIONAL ELECTRIC CODE ANSI/NFPA 70.
The AC input terminals are identified by a red-on-white AC INPUT label, located behind the
access panel on the front of the charger. Removing the top is recommended for ease of
access. The AC input cable is to be connected to the proper AC INPUT terminals within the
charger cabinet. Refer to table 5.3.2 (next page) for input wire size and torque values.