SECTION 8 FAILURE MODE
9.2
BATTERY LOW VOLTS OVERRIDE
If the battery voltage measures less than 1.7 VPC, the charger may be started manually, by
pressing and holding the STOP button for more than 10 seconds. If the battery does not
increase above 1.7 V/Cell in 5 minutes the charger will shut off and indicate Low Volts Alarm
again, otherwise the normal charge cycle will continue. This "grace period" is intended to give
the battery time to recover from its over-discharged condition.
SECTION 9
CHARGER CABINET
SECTION 10
MONTHLY PREVENTIVE MAINTENANCE
11.1
MONTHLY PREVENTIVE MAINTENANCE
WARNING
HIGH VOLTAGES EXIST WITHIN THE CHARGER WHICH CAN CAUSE SEVERE
INJURY OR DEATH. TO ALLOW INTERNAL COMPONENTS TO DISCHARGE,
PLEASE WAIT AT LEAST 3 MINUTES AFTER DISCONNECTING THE AC POWER
BEFORE SERVICING. SERVICE SHOULD ONLY BE PERFORMED BY QUALIFIED
SERVICE PERSONNEL. IMPROPER SERVICING MAY DAMAGE THE CHARGER.
If a battery is being charged, terminate the charge by pressing the STOP button.
Disconnect the battery from the charger.
Remove AC power from the charger.