Inputs and Outputs
SiOne Page
12
Configuration Jumpers
Below is a description of configuration DIP Switches that allows basic configuration of the device.
ON
MODBUS address - configured via jumpers no. 1…5
Address is calculated acc. with formula:
1 + Z1 + Z2*2 + Z3*4 + Z4*8 + Z5*16
,
when Zx (x = 1, 2, …, 5) can be 0 (jumper = OFF) or 1 (jumper = ON)
1 2 3 4 5 6 7 8 9 10
ON
MODBUS baud rate - configured via jumpers no. 6…7
9600 bps : Z6 = 0, Z7 = 0
19200 bps : Z6 = 1, Z7 = 0
38400 bps : Z6 = 0, Z7 = 1
57600 bps : Z6 = 1, Z7 = 1
when Zx (x = 6, 7) can be 0 (jumper = OFF) or 1 (jumper = ON)
1 2 3 4 5 6 7 8 9 10
ON
Analog outputs type - configured via jumpers no. 8…10
Configured via MODBUS : Z8 = 0, Z9 = 0, Z10 = 0
Standard 0…5 V : Z8 = 1, Z9 = 0, Z10 = 0
Standard 0…10 V : Z8 = 0, Z9 = 1, Z10 = 0
Standard 0…20 mA : Z8 = 1, Z9 = 1, Z10 = 0
Standard 4…20 mA : Z8 = 0, Z9 = 0, Z10 = 1
when Zx (x = 8, 9, 10) can be 0 (jumper = OFF) or 1 (jumper = ON).
In case of jumper configuration (not via Modbus), the output standard for all outputs (1, 2 and/or 3) is set equal.
1 2 3
4 5 6 7 8 9 10
Only set the baud rate and MODBUS address when the power is off. New settings will be active as soon as the device is powered.
If you change the settings while the power is on, the new settings will be activated after the device is restarted.