Inputs and Outputs
SiOne Page
11
Analog Outputs (Refer to selected versions)
The SiOne transmitter can be equipped with up to three analog outputs (types of outputs: 0…5 V, 0…10 V, 0…20 mA or 4…20
mA). The types of analog outputs can be changed by configuration jumpers (all outputs configuring together) or by using the
programming unit and service PC software (each output can be programmed separately). Each output can be freely scaled to
the desired measuring range by using the programming unit and service PC software. Output connectors are marked (1 - output
no. 1 (Si-…A1, Si-…A2, Si-…A3 versions), 2 – output no. 2 (Si-…A2, Si-…A3 versions), 3 – output no. 3 (Si-…A3 version). Figure 5
shows a simple scheme of connection the SiOne transmitter to PLC’s analog inputs.
Figure 5. Analog Outputs - Scheme of Connection
Be care when connecting the device. Incorrect connection may damage the device and/or damage other devices that are connecting with
the device.
All connections must only be made with the power off!