A.P.O. - ELMOS v.o.s., Pražská 90, Nová Paka 509 01
tel. +420 493 504 261, fax: +420 493 504 257, e-mail: [email protected]
32
9
FUNCTIONS OF PANELMETER MENU
9.2.3
Configuration of sensors - SEN-1 to SEN-4
Functions SEN-1 to SEN-4 parameters
typ
- Setting of input sensor type
Options:
Signal type
Symbol on display Reference
Figure no.
Input code
Current signal
4 až 20 mA
(passive double-conductor transducer)
4 - 20
fig. 6
34
0/4 až 20 mA
(active current signal)
0 - 20
fig. 7
34
Without sensor
-no-
-no- deactivates sensor and zero is
displayed
Signal type
Symbol on display Reference
Figure no.
Input code
Voltage signal
0 až 10 V
0-10
fig. 8
35
Without sensor
-no-
-no- deactivates sensor and zero is
displayed
Signal type
Symbol on display Reference
Figure no.
Input code
Current/Voltage signal
4 až 20 mA
(passive double-conductor transducer)
4 - 20
fig. 9
36
0/4 až 20 mA
(active current signal)
0 - 20
fig. 10
36
Voltage signal 0 - 10V
0 - 10
fig. 11
36
Without sensor
-no-
-no- deactivates sensor and zero is
displayed
measured value
function selection