APOELMOS AP11-34 Series Manual Download Page 1

www.apoelmos.cz

ISO 9001

PANELMETER AP11

Technical documentation U-19

AP11-34-x-...
AP11-35-x-...
AP11-36-x-...

Summary of Contents for AP11-34 Series

Page 1: ...www apoelmos cz ISO 9001 PANELMETER AP11 Technical documentation U 19 AP11 34 x AP11 35 x AP11 36 x...

Page 2: ...A P O ELMOS v o s Pra sk 90 Nov Paka 509 01 tel 420 493 504 261 fax 420 493 504 257 e mail apo apoelmos cz 2 November 2018 TD U 19 12...

Page 3: ...onnecting of analogue output 17 5 2 Block diagram of analogue output function 18 6 Communication 19 7 Connecting of contact outputs 21 8 Panelmeter functions 21 8 1 Panelmeter switch on 21 8 2 Panelme...

Page 4: ...Paka 509 01 tel 420 493 504 261 fax 420 493 504 257 e mail apo apoelmos cz 4 9 3 Limit values of parameters 39 10 Control software 42 11 ES Declaration of conformity 43 12 Quality certificate 44 13 W...

Page 5: ...n feed current loops of passive sensors is built in panelmeter It can also be equipped with two or four limit switches whose outputs are relay switching contacts Functi ons of switches on multi input...

Page 6: ...e 0 10 V Contact output 0 empty 1 2 x relay switching contacts 250 VAC 2A 2 4 x relay switching contacts 250 VAC 2A Analogue output 0 empty 1 current voltage without galvanic separ 2 current voltage w...

Page 7: ...ax 12 VA Display Display 9999 0 99999 Height of digits 14 mm Decimal point Adjustable with program Bargraph 30 LED Resolution According to position of decimal point Auxiliary power supply 18 VDC 25 mA...

Page 8: ...dity Data back up electrically EEPROM Auxiliary input Voltage free contact keyboard lock Connection Connector terminal board Max section of condu ctor 2 5 mm2 for power supply and contact outputs 1 mm...

Page 9: ...Key SET Key SET is used for setting data programming termination data uploading into EEPROM and return to operating mode 6 Key DOWN Key DOWN is used for browsing parameters and setting of numeric data...

Page 10: ...504 261 fax 420 493 504 257 e mail apo apoelmos cz 10 3 PANELMETER DESCRIPTION fig 3a Dimensions for power supply 80 253 VAC 50 Hz fig 3a Dimensions for power supply 18 36 VDC 18 36 VAC 50 Hz fig 3b f...

Page 11: ...hable constructions blocks as follows connectors 11 to 18 process inputs connectors 21 to 28 analogue output connectors 31 to 38 analogue output and communication connectors 41 to 46 relay output conn...

Page 12: ...250 V Caution Connection of power supply conductors in terminal board Following rules should be observed with designing of the system a All power supply conductors and power lines has to be led separ...

Page 13: ...A 4 chapter limit switch setup ALA 1 to ALA 4 that can be secured with password pass see chapter setting of password PASS men 4 totally disables keyboard no parameter can be set automatic cycling of m...

Page 14: ...ange with function ENDS Connect double conductor transducer to connectors 11 12 13 14 16 as shown on the diagram Connector no 15 is minus Press MENU key and enter apparatus configuration menu browse t...

Page 15: ...tion ENDS Connect double conductor transducer to connectors 11 12 15 as shown on the diagram where con nector no 15 is power supply Press MENU key and enter apparatus configuration menu browse to the...

Page 16: ...nd ending of the range with function ENDS Connect voltage signals to connectors 13 14 16 as shown on the diagram where connector no 16 is common connected to minus Press MENU key and enter apparatus c...

Page 17: ...on display Current 0 20 mA 0 20 4 20 mA 4 20 20 0 mA 20 0 20 4 mA 20 4 Voltage 0 10 V 0 20 2 10 V 4 20 10 0 V 20 0 10 2 V 20 4 Analogue output is commonly connected to position 3 Fig 12 but in case of...

Page 18: ...r orientation In real connection are inputs and setup IN OUT STR END common For correct function of apparatus set range of analogue output STR start of range END end of range that relates to input sig...

Page 19: ...with galvanic separation further referred to as GS 2 x RS485 without GS RS485 with GS RS485 without GS RS485 with GS RS232 Diagram of communication lines RS232 and RS485 connections Diagram of commun...

Page 20: ...ination fig 20 fig 21 Line is terminated at the beginning and the end of communication line to ensure standstill states and to prevent bouncing on line Communication lines RS485 connectors 32 33 a 36...

Page 21: ...switch is not included in panelmeter therefore it activates immediately after to connection to power supply Zero briefly appears on panelmeter display During this time initialization and test of inne...

Page 22: ...isplayed in panelmeter menu On multi input types sum or difference of inputs IN 1 and IN 2 can be set with function IN Functions are indicated as SUBIN and ADDIN Function SUBIN is difference of inputs...

Page 23: ...n Value of limit switch alsp x Setup of limit switch alarm value Required value sp Setup of required value Required value is common for all limit switches and is important only with setting MODE to SH...

Page 24: ...ct the value with UP and DOWN keys and confirm with pressing SET key Further step is setting of re quired value of SP that is designated as SP in configuration menu and is common for all limit switche...

Page 25: ...ted in configuration menu function in e g in 1 Then set value of limit switch ALSP to 10 50 10 switch off limit and function MODE to value SHIFT Set the state of output relay in menu RELE to OFF Set d...

Page 26: ...enu set input with sensor connection function in e g in 1 Then set value of limit switch ALSP to 60 and function MODE to value STATE State of output relay set in RELE menu to OFF Set de activating of...

Page 27: ...ed with parameter LO and top limit with HI With this setting we suppose that required value is located in sector 1 SEC 1 and if it oscillates within set limits display flashes in green If the value fa...

Page 28: ...eters Bargraph relates to measured value that is given by set range STR and END It roughly indicates amount of measured value within limits set by a user Thanks to these properties of bar graph it is...

Page 29: ...Nov Paka 509 01 tel 420 493 504 261 fax 420 493 504 257 e mail apo apoelmos cz 9 FUNCTIONS OF PANELMETER MENU 9 2 Simplified block diagram of panelmeter menu Configuration of inputs that are not conn...

Page 30: ...e shown on the diagrams Press MENU key to enter configuration menu Scroll to required function SP with keys UP and DOWN Press MENU key to enter configuration mode Set required value using keys UP and...

Page 31: ...nce of inputs IN 1 IN 2 IN 3 input 3 IN 4 input 4 TRAL state of relay contacts after alarm conditions subside Options no temporary switching of limit switch after limit switch alarm conditions subside...

Page 32: ...4 0 4 a 20 mA active current signal 0 20 fig 7 34 Without sensor no no deactivates sensor and zero is displayed Signal type Symbol on display Reference Figure no Input code Voltage signal 0 a 10 V 0 1...

Page 33: ...e function sets start of range of input value measurement Parameter is important only with selection of current 4 to 20 mA or 0 to 20 mA or voltage 0 to 10 V input signal ends Setting of ending of inp...

Page 34: ...put Options 0 20 0 to 20 mA 4 20 4 to 20 mA 20 0 20 to 0 mA 20 4 20 to 4 mA str Start of analogue output range end End of analogue output range Example of configuration Press MENU key to enter configu...

Page 35: ...switch on the output err a Setting of analogue output at sensor breakdown Options no Without response to sensor breakdown 0 At breakdown output current 0 mA 20 At breakdown output current 20 mA ERROR...

Page 36: ...word enter code 555 instead to get to new password setting mode Regulator requires password only once in configuration menu If you enter correct password you have free access to all parameters in conf...

Page 37: ...e start This parameter is used for setting the bottom limit of bargraph range When measured value drops to bottom limit of set range all bargraph LEDs stop flashing end Setting of bargraph range end T...

Page 38: ...ng of value top limit when display changes its colour sec 0 Setting of colour for sector 0 sec 1 Setting of colour for sector 1 sec 2 Setting of colour for sector 2 Options G green R red Y yellow mode...

Page 39: ...N ADDIN IN 3 IN 4 IN 1 in 2 Selection of input signal to li mit switch IN 1 IN 2 SUBIN ADDIN IN 3 IN 4 IN 1 In 3 Selection of input signal to li mit switch IN 1 IN 2 SUBIN ADDIN IN 3 IN 4 IN 1 in 4 Se...

Page 40: ...99999 100 0 end 2 End of the range 9999 to 99999 100 0 end 3 End of the range 9999 to 99999 100 0 end 4 End of the range 9999 to 99999 100 0 offs 1 Offset of the range 9999 to 99999 0 offs 2 Offset o...

Page 41: ...A no Parameters Function Limit values Default value Operation a in Setting of analogue input IN 1 IN 2 SUBIN ADDIN IN 3 IN 4 IN 1 a out Type of analogue output 0 20 4 20 20 0 20 4 0 20 a str Start of...

Page 42: ...10 OPERATING SOFTWARE Software PAP is intended for setting of AP21 controller parameters and monitoring of measured values Software available on www apoelmos cz Software Hardware requirements and inst...

Page 43: ...lity system by authorised person no AO 201 Electro technical Testing Institute Pod lisem 129 Prague 8 Troja and monitoring of proper maintaining of the system Above mention product is in compliance wi...

Page 44: ...e period and that are timely claimed The basic condition to be entit led to claim any defect is that the panelmeter is used in the manner specified by technical documentati on Guarantee period is 36 m...