Installation and Operation Manual
ECN: 003155
Date: 06/4/2013
38
AC-SmartStart-7608-Series_IOM Rev 04
LAN Module & Communications
7.6.7 Set PDU and LAN Module to Factory Defaults
Menu option 6 restores all PDU and LAN module defaults back to the factory settings.
This command will ensure that both the LAN module and internal PDU microprocessor
are returned to identical communication settings. If changes are made using the com-
mands in section 5.0 and the PDU is no longer communicating, use this menu selection
to restore internal communications. PDU with LAN modules should have all configuration
changes made using the LAN module configuration menu selections.
7.6.8 Set LAN Module to Factory Defaults
Select 7 to restores all factory settings in the LAN module to the factory default settings.
The server configurations remain unchanged.
7.6.9 Set SNMP Community Strings
Select 8 to change the SNMP community names for read and write. Default settings are
“public” for read and “private” for write. See Figure 7.10.
7.6.10 Set Web Server Port
Select 9 to change the web server port. Default is 80.
7.6.11 Set LAN Module Logging Port
Select 10 to select the command logging port. When enabled, the command-logging
feature will log the last commands received and processed by the PDU. The feature is
used for security and troubleshooting purposes.
Figure 7.10 SNMP Community Strings