![api technologies corp. 7608AD Series Installation And Operation Manual Download Page 11](http://html.mh-extra.com/html/api-technologies-corp/7608ad-series/7608ad-series_installation-and-operation-manual_2953494011.webp)
Installation and Operation Manual
ECN: 003155
Date: 06/4/2013
11
AC-SmartStart-7608-Series_IOM Rev 04
Operational Commands
5.0 Operational Commands
The PDU is shipped with a factory default setting of address FF. All basic commands
would begin with “AFF”. If the unit address is changed to another hex number the
command structure would also change. All control and configuration of the PDU
settings can be changed using the command set below. LAN module configuration
can only be performed through the LAN connection. Please see section 7.0 for LAN
module configuration.
The basic commands are valid only when the PDU is in the “remote” mode and the
user is communicating using RS-232, RS422/485 or Telnet. If an external software
program is used to issue commands, a delay of 10 milliseconds should be used be-
tween characters and 40 milliseconds between commands being sent should be used.
If the user is typing the commands below, no delays are necessary as the communi-
cation scheme can keep up with the speed of the human interface.
PDU Commands
The following commands are based on factory default settings. All commands must be followed by
a carriage return. For 1X8 units use the “A” commands, for 2X4 units use the “A” and “B” com-
mands.
Command
Explanation
Response
BAUD RATE
AFFB
Returns current baud rate setting
UFFB1
AFFB0
Set baudrate to 4,800 bps
UFFB0
AFFB1
Set baudrate to 9,600 bps
UFFB1
AFFB2
Set baudrate to 19,200 bps
UFFB2
AFFB3
Set baudrate to 38,400 bps
UFFB3
If a LAN module is present do not use this command.
Use the LAN module configuration menu on telnet port
9999 menu choice 1 “Channel 1
configuration”
EXTERNAL CONTACTS
(Bot row pins 6, 7, 8) When the PDU is powered on all
external contact relays are turn on.
AFFCA
Returns the setting of the external contact configuration. UFFCA FF
AFFCA FF
Sets external contacts to monitor undervoltage condition
on channel A (see AFFUA command for setpoint details)
UFFCA FF
AFFCA DD
Sets external contacts to monitor overcurrent condition
on channel A (see AFFLA command for setpoint details)
UFFCA DD
AFFCA CC
Sets external contacts to monitor overtemperature con-
dition (see AFFK command for setpoint details)
UFFCA CC
AFFCA 00
Sets external contacts to the OFF position.
UFFCA 00
AFFCA 01
Sets external contacts to the ON position.
UFFCA 01