Installation and Operation Manual
ECN: 003155
Date: 06/4/2013
24
AC-SmartStart-7608-Series_IOM Rev 04
Windows Configuration & Control Utility
Figure 6.10 Global PDU Status Window
6.5 CONTROL WINDOW
The Control window allows the user to turn individual outlets off or on, sequence the
outlets off or on, and change the PDU control settings. When using the outlet buttons
to control the outputs, the PDU will remember the state of the outlets when power is
removed and then re-applied. Those outlets that were turned off will remain off. If the
sequence off button is used, all outlets that were in the on state prior to sequencing off
will sequence back on by selecting the sequence on button or with the removal and re-
application of AC input power.
6.6 PDU PROPERTIES
By clicking on the PDU Settings tab in the Control window, this will display all of the
current settings of the PDU. The PDU properties are categorized into four tabs titled
Sequencing, Communication, Alarm Settings, and Auxiliary I/O. These settings can also
be changed here.
6.6.1 PDU Sequencing Properties
The sequencing window allows the user to change the order that the outputs will se-
quence on and the time delay between each output turning on. The reverse order and
same time delay is used during a down sequence. Setting an "O" in any sequence posi-
tion box in Figure 6.11, will set that position to a manual operation mode.