Analog Low (AL CAL) & Analog High (AH CAL) Calibration:

Allows the user to calibrate or “trim” the endpoints of the analog signal 
output (i.e. 4mA & 20mA or 0V & 2V/5V)

Calibrating the Analog Signal End-Points:

Step 1: 

Use a calibrated meter to monitor the analog output signal.

 

Step 2: 

Force a low analog output signal (i.e. 4mA or 0V) either by adjusting 

the applied pressure or by adjusting the Analog Setpoints (see “Analog 
Low & Analog High Setpoints” on page 20 for details).

 

Step 3: 

Press the 

On/Off

 button once to enter the main setup menu.

 

Step 4: 

Press 

(Z)

 to cycle through the options until 

Output 

is displayed.

Step 5: 

Press 

(S)

 to access the Output Settings menu.

Step 6: 

Press 

(Z)

 to cycle through the setup options until 

AL CAL

 is 

displayed.

Step 7: 

Press 

(S)

 to access the Analog Low Calibration value. A 5-digit 

number will appear with the first digit flashing.

Step 8: 

Press 

(Z)

 to change the value of the flashing digit. 

 

NOTE: 

Increasing this 5-digit number will increase the output signal. 

Changing the digit farthest to the left will produce the coarsest adjustment, 

while each successive digit moving to the right will cause subsequently finer 

adjustments to the output signal.
 

  

Step 9: 

Press 

(S)

 to accept the value of the flashing digit and advance to the 

next digit. Repeat steps 6 and 7 until the desired Analog Output signal 
is displayed on the meter. After the last digit is accepted by pressing 

(S)

, the display will return to the output menu.

Step 10: 

Press 

(S)

 to reenter the Output Settings menu.

Step 11: 

Press 

(Z)

 to cycle through the options until 

AH CAL

 is displayed.

Step 12: 

Repeat Steps 5-7 to adjust the Analog High Calibration value.

Step 13: 

To exit the output menu, press 

(Z)

 until 

EXIT

 is displayed and press 

(S) 

to exit to the main setup menu.

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for PG-7

Page 1: ...Operator s Manual AUTOMATION P R O D U C T S GROUP INC Automation Products Group Inc PG 7 Full Access DOC 9003312 Rev A2 07 16 www com information itm 0 561 8187 ...

Page 2: ...Minimum Reset 8 Units of Measure 9 Using Custom Units 10 Peak Hold Feature 11 Advanced Settings 12 17 Auto Off 12 Decimal Place 13 Sample Rate 14 Bar Graph 15 Range Adjustment 16 Quick Calibration 17 Tare Feature 18 Default 19 Output 20 24 Setting Calibrating Analog Signal Span End Points 20 21 Trip Points 22 24 Wiring 25 26 Specifications 27 28 Declaration of Conformity 29 30 www com information ...

Page 3: ... Primary Function Cycles between the current maximum and minimum pressure readings Secondary Function Used to accept the displayed option while in the setup menus Secondary Function Resets the peak hold reading when the peak hold feature is enabled Each of the three buttons on the PG7 performs multiple functions The primary function applies when in standard operating mode The secondary functions a...

Page 4: ...OW CALIBRATION SET ANALOG HIGH CALIBRATION Menu options only available for gauges with an analog output or relays T1TYPE T1PRES TYPE0 TYPE1 TYPE2 TYPE3 TYPE4 TYPE5 SET TRIP PRESSURE 1 START PRESSURE T1WIN T2TYPE SET TRIP PRESSURE 1 WINDOW SIZE TYPE0 TYPE1 TYPE2 TYPE3 TYPE4 TYPE5 T2PRES T2 WIN SET TRIP PRESSURE 2 START PRESSURE SET TRIP PRESSURE 2 WINDOW SIZE EXIT CALIBR FAST CALIBRATE ZERO AND SPA...

Page 5: ...nce to the next digit Mode Definitions Mode 000 Full Access Provides access to all menu settings If no buttons are pushed for 1 minute the gauge will revert back to Mode 003 factory default Mode 002 Limited Access Menu is locked Z button zeros the reading S cycles between the Max and Min readings On Off functions only on battery powered gauges Mode 003 Factory Default Full access except Full Scale...

Page 6: ...e next digit change the mode number to 000 Step 3 Press On Off to enter the setup menu and press Z to scroll through menu choices Exiting the Setup Menu Step 1 While in the main setup menu press Z until EXIT is displayed Step 2 Press S to access the Exit options Step 3 Press Z until YES is displayed Step 4 Press S to Exit the main setup menu and return to the standard operating mode Zero Z Button ...

Page 7: ...ings will be stored until the gauge is powered down or the max min readings are reset Resetting the Max Min readings Step 1 Press the On Off button once to enter the main setup menu Step 2 Press Z to cycle through the options until MAXMIN is displayed Step 3 Press S to access the Max Min reset options Step 4 Press Z to toggle between YES and NO until YES is displayed Step 5 Press S to reset the Ma...

Page 8: ...ss than 120 psi PSI pounds per square inch bAR bar KPA kilopascals CUSTOM see Using Custom Units on next page mbAR millibar INHG inches of mercury INH20 inches of water 60 F mmHG millimeters of mercury Setting the Unit of Measure Step 1 Press the On Off button once to enter the main setup menu Step 2 Press Z to cycle through the options until UNITS is displayed Step 3 Press S to access the Units o...

Page 9: ...le through the options until UNITS is displayed Step 4 Press S to access the Units setting options Step 5 Press Z to cycle through the Units options until CUSTOM is displayed Step 6 Press S to access the Custom Units setting A 5 digit conversion factor will appear with the first digit flashing Step 7 Press Z to change the value of the flashing digit options 0 9 Step 8 Press S to accept the flashin...

Page 10: ...played in the upper left corner of the display Options Off or On Enabling the Peak Hold feature Step 1 Press the On Off button to enter the main setup menu Step 2 Press Z to cycle through the options until P HOLd is displayed Step 3 Press S to access the Peak Hold setting options Step 4 Press Z to toggle between OFF and ON Step 5 Press S to apply the displayed setting and return to main setup menu...

Page 11: ... powered indefinitely as long as there is sufficient voltage being supplied 1 8V Setting the Auto Off feature Step 1 Press the On Off button to enter the main setup menu Step 2 Press Z to cycle through the menu options until AdVSET is displayed Step 3 Press S to enter the Advanced Settings menu Step 4 Press Z to cycle through the menu options until AUTO is displayed Step 5 Press S to access the Au...

Page 12: ...ution or LO RES low resolution Setting the Decimal Place feature Step 1 Press the On Off button to enter the main setup menu Step 2 Press Z to cycle through the options until AdVSET is displayed Step 3 Press S to enter the Advanced Settings menu Step 4 Press Z to cycle through the options until dEC PL is displayed Step 5 Press S to access the Decimal Place setting options Step 6 Press Z to cycle t...

Page 13: ...enter the main setup menu Step 2 Press Z to cycle through the options until AdVSET is displayed Step 3 Press S to access the Advanced Settings menu Step 4 Press Z to cycle through the options until SAMPLE is displayed Step 5 Press S to access the Sample Rate setting options Step 6 Press Z to cycle through the setting options until the desired setting is displayed Step 7 Press S to apply the displa...

Page 14: ... the options until AdVSET is displayed Step 3 Press S to access the Advanced Settings menu Step 4 Press Z to cycle through the options until BAR 0 is displayed Step 5 Press S to access the Bar Graph 0 value A 5 digit number will appear with the first digit flashing Step 6 Press Z to change the value of the first flashing digit options 0 9 or Step 7 Press S to accept the value of the flashing digit...

Page 15: ...ange Adjusting the Full Scale Range Step 1 Ensure that the pressure reading is within 5 of full scale Step 2 Press the On Off button to enter the main setup menu Step 3 Press Z to cycle through the options until AdVSET is displayed Step 4 Press S to access the Advanced Settings menu Step 5 Press Z to cycle through the options until RANGE is displayed Step 6 Press S to enter the Range adjust mode S...

Page 16: ...Step 4 Press Z to cycle through the options until CALIBR is displayed Step 5 Press S to access the CALIBR mode The gauge will display the word ZERO prompting the user to perform the zero pressure quick calibration Step 6 Ensure no pressure is applied to the gauge Press Z to zero the gauge The gauge will then display the word SPAN prompting the user to perform the full scale pressure quick calibrat...

Page 17: ...y the displayed option and return to main setup menu NOTE 1 When tare function is enabled the T5 symbol will appear in the lower left corner of the display WARNING Do NOT disconnect the gauge from the pressure fitting while the tare function is enabled The gauge could still be under pressure even though the reading shows 0 NOTE 2 If the maximum gross full scale pressure value is reached while the ...

Page 18: ...y default settings Step 1 Press the On Off button once to enter the main setup menu Step 2 Press Z to cycle through the options until dEFAUL is displayed Step 3 Press S to access the Default options Step 4 Press Z to cycle between NO and YES Step 5 Press S to apply the displayed setting and return to main setup menu www com information itm 0 561 8187 ...

Page 19: ...u Step 4 Press Z to cycle through the options until AL SET is displayed Step 5 Press S to access the Analog Low setpoint value A 5 digit number will appear with the first digit flashing Step 6 Press Z to change the value of the first flashing digit options 0 9 or Step 7 Press S to accept the value of the flashing digit and advance to the next digit Repeat steps 6 and 7 until the desired Analog Low...

Page 20: ...alog Low Calibration value A 5 digit number will appear with the first digit flashing Step 8 Press Z to change the value of the flashing digit NOTE Increasing this 5 digit number will increase the output signal Changing the digit farthest to the left will produce the coarsest adjustment while each successive digit moving to the right will cause subsequently finer adjustments to the output signal S...

Page 21: ...Trip Window Type 2 or Normally Closed with Hysteresis setting will close the trip relay when the pressure drops below the Trip Pressure Once closed the trip relay will remain closed until the pressure becomes greater than the Trip Pressure Trip Window at which point the trip relay will open Once open the trip relay will remain open until the pressure once again drops below the Trip Pressure settin...

Page 22: ...up Inc Trip Pressure determines the lower pressure point for the trip output function Trip Window determines the pressure range between the lower and upper trip pressures Used for Types 1 2 4 5 see chart below www com information itm 0 561 8187 ...

Page 23: ...s Z to change the value of the first flashing digit options 0 9 or Step 11 Press S to accept the value of the flashing digit and advance to the next digit Repeat steps 10 and 11 until the desired Trip Pressure is fully entered After the last digit is accepted by pressing S the display will return to the Output Settings menu Step 12 Press Z to cycle through the Output menu options until T1WIN or T2...

Page 24: ...inimum is 5 V 9 V 14V NOTE 2 Completion of the earth ground Pin F is recommended for proper circuit protection Battery Replacement Step 1 Press on the front bezel and turn counter clockwise to release the bezel from the gauge Step 2 Remove the front display to access the batteries Step 3 Replace the front display ensuring that the notch in the display aligns with the tab on the gauge housing Step ...

Page 25: ...n C Output 1 T1 D Output 1 T1 E Output 2 T2 F Output 2 T2 NOTE Output 1 corresponds to T1 on the LCD display while Output 2 corresponds to T2 Pinouts for Outputs with Relays 4 20 mA or Ext Power 0 2 VDC or 0 5 VDC 0 2 VDC with Ext Power Pin A Excitation Excitation Excitation Pin B Excitation Output Output Pin C Trip 1 Excitation Excitation Pin D Trip 1 Trip 1 Trip 1 Pin E Trip 2 Relay Common Relay...

Page 26: ...inearity hysteresis 0 25 B F S L Environmental Housing IP67 Compensated Temp 20 to 1300 F 7 to 540 C Storage Temp 40 to 1600 F 40 to 710 C Operating Temp 0 to 1600 F 18 to 710 C Electrical Batteries 2 Standard AA 1 Lithium AA External Power 9 28 VDC Physical Weight 0 42 lb Case Material Injection molded material EMI X PDX W 88341 www com information itm 0 561 8187 ...

Page 27: ...Zero set point is 0 15 V with a 2 VDC span 0 02 VDC Wiringt 2 wire Resolution 14 bit 0 5 VDC Output Input Voltage Excitation 9 to 28 VDC Input Current 6 mA max Output 0 5 VDC 0 5 VDC at set points Wiring Non isolated 3 wire Resolution 14 bit Protection Reversed polarity RS 485 Output Input Voltage Excitation 12 to 28 VDC Input Current 6 mA max Output Modbus RTU Wiring 4 wire Protection Reversed po...

Page 28: ...Rev A2 07 16 PG7 29 Automation Products Group Inc www com information itm 0 561 8187 ...

Page 29: ...PG7 Rev A2 07 16 30 Automation Products Group Inc www com information itm 0 561 8187 ...

Page 30: ...t 9003312 Rev A21 07 16 P R O D U C T S GROUP INC Automation Products Group Inc Tel 1 888 525 7300 1 435 753 7300 Fax 1 435 753 7490 e mail sales apgsensors com www apgsensors com Automation Products Group Inc 1025 W 1700 N Logan UT 84321 www com information itm 0 561 8187 ...

Reviews: