Bar Graph 0% (bAR 0) & Bar Graph 100% (bAR100)
Settings:
Allows the user to define the reading values associated with 0%
and 100% on the display bar graph. Bars will appear/disappear in
10% increments of the total span between the two values.
NOTE:
The 0% reference does not have to be the lower pressure setting; 0%
can be set as the higher pressure setting, thereby causing the bar graph to
increase as the pressure decreases. Negative pressure settings can also be
used as either the 0% or 100% reference points.
Setting the Display Bar Graph:
Step 1:
Press the
On/Off
button once to enter the main setup menu.
Step 2:
Press
(Z)
to cycle through the options until
AdVSET
is displayed.
Step 3:
Press
(S)
to access the Advanced Settings menu.
Step 4:
Press
(Z)
to cycle through the options until
BAR 0
is displayed.
Step 5:
Press
(S)
to access the Bar Graph 0% value. A 5-digit number will
appear with the first digit flashing.
Step 6:
Press
(Z)
to change the value of the first flashing digit (options: 0-9
or “-”).
Step 7:
Press
(S)
to accept the value of the flashing digit and advance to the
next digit. Repeat steps 6 and 7 until the desired 0% reading is fully
entered. After the last digit is accepted by pressing
(S)
, the display will
return to the advanced setup menu.
Step 8:
Press
(Z)
to cycle through the options until BAR100 is displayed.
Step 9:
Repeat Steps 5-7 to enter the Bar Graph 100% value.
Step 10:
To exit the advanced setup menu, press
(Z)
until
EXIT
is displayed
and press
(S)
to exit to the main setup menu.