PG7
Rev. A2, 07/16
16
Automation Products Group, Inc.
Full-Scale Range Adjust (RANGE):
Allows the user to adjust the reading at full-scale pressure. The reading can
be adjusted by +/-10% full-scale.
NOTE:
The pressure reading must be within 5% of the full-scale value in
order to make Range adjustments. For example, a 1000 psi gauge would
need to be reading between 950 psi and 1050 psi in order to adjust the
Range feature. If the reading is not within 5% of full scale, NOAdJU (No
Adjustment) will be displayed when trying to adjust the Range.
Adjusting the Full-Scale Range:
Step 1:
Ensure that the pressure reading is within 5% of full-scale.
Step 2:
Press the
On/Off
button to enter the main setup menu.
Step 3:
Press
(Z)
to cycle through the options until
AdVSET
is displayed.
Step 4:
Press
(S)
to access the Advanced Settings menu.
Step 5:
Press
(Z)
to cycle through the options until
RANGE
is displayed.
Step 6:
Press
(S)
to enter the Range adjust mode.
Step 7:
Press
(Z)
to
increase
the reading, or press
(S)
to
decrease
the
reading.
Step 8:
Press the
On/Off
button to accept the adjusted reading and return
to the advanced setup menu.
Step 9:
To exit the advanced setup menu, press
(Z)
until
EXIT
is displayed
and press
(S)
to exit to the main setup menu.