40422 - Float Window (Factory Calibrated)
Sets the distance (0 - 1000 mm) between the first (i.e. top) float and the point at which the sensor will begin
looking for the second (bottom) float. 0 indicates a single float.
40424 - 2nd Float Offset (Factory Calibrated)
Used to calibrate bottom float reading (-10,364 - 10,364 mm). Differences in fluid specific gravity can change
the level at which a float rests in the liquid. Use this parameter to match probe reading to confirmed liquid
level.
40423 - 1st Float Offset (Factory Calibrated)
Used to calibrate top float reading (-10,364 - 10,364 mm). Differences in fluid specific gravity can change the
level at which a float rests in the liquid. Use this parameter to match probe reading to confirmed liquid level.
40425 - Gain Offset (Factory Calibrated)
Used to move the centerline of the float response signal to optimize signal strength (0 - 255).
40446 - Baud Rate
Selects the communication speed between the sensor and the Server Device. All devices on the network
must use the same Baud Rate.
APG Modbus Server and Client devices default to 9600 Baud.
0 = 9600
1 = 19200
2 = 38400
3 = 57600
4 = 115200
40201 - Restore To Factory Defaults
Writing a 1 to this Holding Register will erase any settings changes and restore the factory default settings.