40405 - Maximum Distance (Factory Calibrated)
Sets the distance (beginning from the Zero Reference) to the point where the sensor will stop looking for
float signals, usually the bottom of the stem. A float beyond the Maximum Distance value will not be detect
-
ed.
40406 - Full Distance
Sets the positive distance (beginning from the sensor Zero Reference) to the point where the monitored
vessel is considered full.
40407 - Empty Distance
Sets the positive distance (beginning from the Zero Reference) to the point where the monitored vessel is
considered empty (usually the bottom of the stem).
40408 - Sensitivity (Factory Calibrated)
Sets the level of gain that is applied to the returning float signal.
40409 - Pulses (Factory Calibrated)
Controls the duration of the signal being sent down the magnetostrictive wire.
40410 - Blanking (Factory Calibrated)
S
ets the blanking distance, which is the zone from the Zero Reference of the sensor to the point from which
the first signal will be valid. Signals from a float in the blanking area will be ignored.
40412 - Averaging (Factory Calibrated)
S
ets the number of qualified received float signals to average for the raw reading. Qualified received signals
are placed in a first-in, first-out buffer, the contents of which are averaged for the raw reading. The larger
the number of qualified received signals being averaged, the smoother the reading will be, and the slower
the reading will be to react to quickly changing targets.