APEN GROUP SPA reserves the right to contribute the necessary modifications to the documentation or documentation
44
cod. HG0130.05GB ed.B-2104
PCH
45
cod. HG0130.05GB ed.B-2104
PCH
PCH cold storage generator module
TYPE OF GAS G30 - Cat. 3B-P
TYPE OF MACHINE
PCH020
PCH034
PCH045
PCH065
PCH080*
PCH105**
Output
min
max min max min max min max min
max
min
max
CATEGORY
according to the country of destination - see reference table
SUPPLY PRESSURE
[mbar]
30 [min 25-max 35] - 50 [min 42.5-max 57.5]
PILOT NOZZLE Ø
[mm]
0.51
GAS CONSUMPTION
(15°C-1013mbar)
[kg/h]
0.40 1.58 0.63 2.90 0.71 3.49 1.03 5.39 1.49 6.80 1.70 8.30
CARBON DIOXIDE -CO
2
CONTENT
[%]
10.8 11.4 10.8 11.5 10.8 10.9 10.7 11.3 10.1 10.3 10.4 10.6
FLUE GAS TEMPERATURE
[°C]
39
113
31
94
30
94
31
86
26.5
70
28
80
GAS ORIFICE PLATE
[mm]
3.7
4.4
5.2
6.5
7.0
9.3
AIR ORIFICE PLATE
[mm]
Not
required
Not
required
Not
required
Not
required
Not
required
Not
required
* Minimum rated heat output 18 kW
** Minimum rated heat output 24 kW
TYPE OF GAS G31 - Cat. 3P
TYPE OF MACHINE
PCH020
PCH034
PCH045
PCH065
PCH080
PCH105
Output
min
max min max min max min max min
max
min
max
CATEGORY
according to the country of destination - see reference table
SUPPLY PRESSURE
[mbar]
30 [min 25-max 35] - 37 [min 25-max 45] - 50 [min 42.5-max 57.5]
PILOT NOZZLE Ø
[mm]
0.51
GAS CONSUMPTION
(15°C-1013mbar)
[kg/h]
0.39 1.55 0.62 2.85 0.70 3.43 1.01 5.31 1.34 6.70 1.47 8.18
CARBON DIOXIDE -CO
2
CONTENT
[%]
9.3
9.8
9.2
9.7
9.3
9.4
9.4
9.6
9.3
9.6
9.5
9.8
FLUE GAS TEMPERATURE
[°C]
39
113
31
94
30
94
31
86
26.5
70
28
80
FLUE GAS MASS FLOW
RATE (MAX.)
[kg/h]
24
45
58
84
107
130
GAS ORIFICE PLATE
[mm]
3.7
4.4
5.2
6.5
7.0
9.3
AIR ORIFICE PLATE
[mm]
Not
required
Not
required
Not
required
Not
required
Not
required
Not
required
NOTE:
For PCH130 and PCH132 gas consumption and mass flow rate values are twice the PCH065 values.
For PCH 160 and PCH162 gas consumption and mass flow rate values are twice the PCH080 values.
For PCH 210 and PCH212 gas consumption and mass flow rate values are twice the PCH105 values.
For PCH320 gas consumption and mass flow rates are three times higher than the PCH105.
For PCH420 gas consumption and mass flow rates are three times higher than the PCH105.