PCH cold storage generator module
10m
HG0130.00 A 040
HG0130.00 A 039
HG0130.00 A 038
Gas pipe installation
Special attention must be paid when fitting the gas supply
pipes to allow the burner housing door to open, as shown
in
the figures below
.
---------------------------------------------------------------------------------
If pressure is higher than 60mbar, a pressure reducer
must be installed at a distance of at least 10m and no
pressure stabiliser must be fitted between the pressure
reducer and the heater, but leaving the gas filter.
---------------------------------------------------------------------------------
NO
YES
Pressure reducer
↑
Max 60 mbar