Page 24 code HG0109.12GB ed.C-1106 rev.12
APEN GROUP reserves the right to change products and documents as required.
WARM AIR HEATER SERIES RAPID
HG0100 C2 012
Wiring G12800 remote control
G12800 remote control includes an I/O switch, a summer/
winter switch, a reset and lock signaling LED and is delivered
with a multipole, numbered cable already wired.
To wire the control to the heater, do the following:
- Wire remote control numbered wires (1 to 6) to 31-36 terminals
of relevant board (see diagram in this page).
- Make sure the summer/winter switch installed on the heater
is turned on "I=WINTER".
HG0109.12 C2 003
Wiring G00094 remote control
G00094 remote control includes a room thermostat, a summer/
winter switch, a reset and lock signaling LED and is delivered
with a multipole, numbered cable already wired.
To wire the control to the heater, do the following:
- Wire remote control numbered wires (2 to 6) to 31-36 terminals
of relevant board (see diagram in this page).
- Make sure the summer/winter switch installed on the heater
is turned on "I=WINTER".
HG109.12 C2 002
REMARK: Do not use a multipole cable
conducting both electrical supply and
chronothermostat control, since this would
interfere with control signals, jeopardizing
heater operation.
DO NOT CONNECT
AND
ISOLATE POWER
CABLE
REMARK: Do not use a multipole cable
conducting both electrical supply and
chronothermostat control, since this would
interfere with control signals, jeopardizing
heater operation.
HG0109.12_C2_026