Page 21
APEN GROUP reserves the right to change products and documents as required.
code HG0109.12GB ed.C-1106 rev.12
WARM AIR HEATER SERIES RAPID
** using Ø100/80 male/female adapters
*** using Ø80/100 male/female adapters
L2
L1
Terminals include:
• TB23-08-VS0 -Rain protection Ø80
-Extension Ø80 L=1000mm
-Elbow Ø80 90°
• TC00-08-HS0 -Intake terminal Ø80 with grid
-Outer and inner wall plates
-Fastening accessories
• TB23-10-VS0 --Rain protection Ø100
-Extension Ø100 L=1000mm
-Elbow Ø100 90°
• TC00-10-HS0 --Intake terminal Ø100 with grid
-Outer and inner wall plates
-Fastening accessories
15
14
13
11
HG0103 C2 015
C53 TYPE Sealed combustion circuit from the room. Pipe systems are connected one to the roof and the
other to the wall.
HG0109.12_ET_012
Max L1 + L2 of layout, terminal excluded
Discharge Ø80 TB23-
08-VS0
Intake Ø80 TC00-08-HS0
Discharge Ø100 TB23-08-
VS0
Intake Ø100 TC00-08-HS0
Pipes and elbows Ø80 Pipes and elbows Ø100
Model
Meters
RA015
14 + 14
RA024
13 + 13
RA032
13 + 13
RA035
11,5 + 11,5
RA043
9 + 9
RA054
7 + 7
12,5 + 12,5***
REMARK: Max possible length was equally divided between intake and
discharge. Different ratios are allowed, provided the maximum value shown in
the table is not exceeded.