45
TC5-1V6SA.rev.06
TC5-1V6SA
3
Adjusting Max. Temperature Difference Between
Zones
When using zoned heating, a built-in protection will operate the fans accord-
ing to the probes of the zone with the highest temperature whenever the
temperature difference between zones is greater than this parameter. The
default value is 7.5°F (4.2°C) and values range from 5°F to 40.0°F (2.8°C to
22.2°C).
n
Set the selection knob to
HEATER 2 — OFF./DIFF.
The current heater
offset is displayed, alternating with the letters "
OFT
".
n
Press the push-button twice. The maximum temperature difference
between zones is displayed, alternating with the letters "
dif Zon
".
n
Use the adjustment knob to adjust the temperature difference to the
desired value.