38
TC5-1V6SA.rev.06
TC5-1V6SA
ON
OFF
TIME ON
TIME OFF
If the humidity compensation is activated, the mist units are turned off
when the humidity reaches a user-defined maximum humidity level.
The mist units operate according to a timer cycle. Time on is the running
time of the mist units and time off is the off time of the mist units.
M
IST COOLING
NUMBER OF HEATING STAGES
MIST STAGE
0
7
1
6
2
5
The last cooling stage can be configured as a mist stage. The number of
heating stages determines which stage this is. To activate mist cooling, set
internal switch # 9 to ON.
Mist units turn off
Room
Temperature
Set Point
Mist
Mist Offset
OFF
Mist units turn on
in timer mode
Diff.
The following diagram sums up the operation of the mist units.