47
TC5-1V6SA.rev.06
TEST MODE
A test mode allows you to simulate temperature changes and verify control-
ler performance. In test mode, the temperature probe inputs are turned off,
allowing the user to change the temperature used by the controller to oper-
ate the stages. The controller operates as before using the new tempera-
ture settings.
To enter test mode:
n
Turn the selector knob to the
ROOM TEMPERATURE
position. The
current room temperature is displayed.
n
Press and hold the push-button for 3 seconds. The letters "
TST
" are
displayed, alternating with the room temperature.
n
Turn the adjustment knob to adjust the room temperature to the de-
sired value. The controller operates the stages according to the new
temperature setting.
To exit test mode:
n
Turn the selector knob to the
ROOM TEMPERATURE
position. The
current room temperature is displayed.
n
Press and hold the push-button for 3 seconds.
NOTE:
If no user activity is recorded after 4 minutes in test mode, the
controller resumes normal operation.