VENTILATION SETTINGS
•
When
room temperature < Set Point
, stage 1 fans run at minimum
speed according to the minimum ventilation cycle.
•
At Set Point
: stage 1 fans stop operating according to the minimum
ventilation cycle and increase in speed as the room temperature rises.
•
At Set Point + Bandwidth 1
: stage 1 fans reach full speed.
•
At Set Point + ban diff. 2
: stage 2 fans start running.
•
At Set Point + ban diff. 2 + diff. 3
: stage 3 fans start running.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4
: stage 4 fans start
running.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5
: stage
5 fans start running.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6
: stage 6 fans start running.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6 + diff. 7
: stage 7 fans start running.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6 + diff. 7 + diff. 8
: stage 8 fans start running.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6 + diff. 7 + diff. 8 + diff. 9
: stage 9 fans start running.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6 + diff. 7 + diff. 8 + diff. 9 + diff. 10
: stage 10 fans start running.
The TC5-1V10SA controls one stage of variable-speed fans (Stage1), eight
stages of constant-speed fans (Stages 2 - 9) and two optional stages of
constant-speed fans (Stages 10 & 11). The diagram on the following page
shows the operation of the cooling stages.