40
TC5-1V10SA rev.06
TC5-1V10SA
1
Adjusting Mist Differential
The mist differential is the variation in room temperature between the moment
the mist units turn on and the moment they turn off.The differential can be
adjusted between 0.5°F and 20.0°F (0.3°C and 11.1°C).
n
Set the parameter selection
knob to
MIST — TIMER/OFF-
SET
. The current time on for
the mist cycle is displayed,
alternating with the letters
"
On
".
n
Press the push-button three
times. The mist differential is
displayed, alternating with the
letters "
dIF
",
n
Using the adjustment knob, set the differential to the desired value.
2
Adjusting Mist Offset
The mist offset is the temperature difference from the set point at which the
mist units turn off. The offset can be adjusted between 0.5°F and 40.0°F
(0.3°C and 22.2°C).
n
Set the parameter selection knob to
MIST — TIMER/OFFSET
.
The current time on for the mist cycle is displayed, alternating
with the letters "
On
".
n
Press the push-button twice. The mist offset is displayed, alternating
with the letters "
Oft
".
n
Using the adjustment knob, set the offset to the desired value.