24
TC5-1V10SA rev.06
TC5-1V10SA
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6 + diff. 7 + diff. 8 + diff. 9 + diff. 10 + diff. 11
: stage 11 fans start
running.
If the room temperature falls:
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6 + diff. 7 + diff. 8 + diff. 9 + diff. 10
: stage 11 fans return to a stop.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6 + diff. 7 + diff. 8 + diff. 9
: stage 10 fans return to a stop.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6 + diff. 7 + diff. 8
: stage 9 fans return to a stop.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6 + diff. 7
: stage 8 fans return to a stop.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5 + diff.
6
: stage 7 fans return to a stop.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4 + diff. 5
: stage
6 fans return to a stop.
•
At Set Point + ban diff. 2 + diff. 3 + diff. 4
: stage 5 fans
return to a stop.
•
At Set Point + ban diff. 2 + diff. 3
: stage 4 fans return to a
stop.
•
At Set Point + ban diff. 2
: stage 3 fans return to a stop.
•
At Set Point + bandwidth
: stage 2 fans return to a stop; stage 1
fans start decreasing in speed as the temperature decreases.
•
At Set Point:
stage 1 fans reach minimum speed.
•
Below the Set Point
: stage 1 fans stop operating continuously and
operate according to the minimum ventilation cycle at minimum speed.