Ozone Detector c/w
O3TH
Dec.11
Automatikprodukter
Indicator for Temperature/Humidity
LCD Display
Parameter
Setting Range
Default
-05
Un-effective for the model
0
- 06
Minus differential of ozone
5 -30
20
of control the delay e.g. the
setting value is 10 and O3 is
50ppb, if measured O3<50-10ppb,
the relay will be on (DIP4=OFF)
or will be off (DIP4=ON).
-07
Positive differential of ozone of
5 - 100
50
’
control the delay e.g. the setting
value is 20 and O3 setting is 50ppb,
if measured O3>50+20ppb, the relay
will be off (DIP4=OFF) or will be on
(DIP4=ON).
-08
The state of the detector electrify
0: turn off after electrify
2
after power broken
1: turn on after electrify
2: keep on the last state
-09
Setting RS485 address
0-250
0
-10
RS485 communication rate selection
1: 9600bps
2: 14400bps
3
3: 19200bps 4: 28800bps
5: 38400bps
RESET:
Put the DIP1 to ON and press switch key for about 25 seconds until the detector is off, then all the setting return to the
default.
Annex: Ozone Measurement Emendation
Put the four DIPs to the upper position to be ON and then start ozone emendation.
1) The digit displayed on the upper left of the LCD indicates the demarcation point that is right now being
emended.
Display range: 01, 02, 03, 04, 05, 06, 07, 08, 09, 10
2) The digit displayed on the upper right of the LCD indicates the ozone measurement at the current demarcation point.
Display range: Y1, Y2, Y3, Y4, Y5, Y6, Y7, Y8, Y9, Y10
3) The digit displayed on the bottom line corresponds to the A/D transition level of X axial.
4) The non-twinkling figure indicates the real-time ozone measurement detected by the sensor.
5) The twinkling figure indicates the demarcation point that needs to be set
Display range: X1, X2, X3, X4, X5, X6, X7, X8, X9, X10