Ozone Detector c/w

O3TH

Dec.11

    Automatikprodukter

Indicator for Temperature/Humidity

        LCD Display

Parameter

Setting Range

Default

-05

Un-effective for the model

0

- 06

Minus differential of ozone

5 -30

20

of control the delay e.g. the

setting value is 10 and O3 is

50ppb, if measured O3<50-10ppb,

the relay will be on (DIP4=OFF)

or will be off (DIP4=ON).

-07

Positive differential of ozone of

5 - 100

50

control the delay e.g. the setting

value is 20 and O3 setting is 50ppb,

if measured O3>50+20ppb, the relay

will be off (DIP4=OFF) or will be on

(DIP4=ON).

-08

The state of the detector electrify

0: turn off after electrify

2

after  power  broken

1: turn on after electrify

2: keep on the last state

-09

Setting RS485 address

0-250

0

-10

RS485 communication rate selection

1: 9600bps

2: 14400bps

3

3: 19200bps 4: 28800bps

5: 38400bps

RESET:

 Put the DIP1 to ON and press switch key for about 25 seconds until the detector is off, then all the setting return to the

default.

Annex: Ozone Measurement Emendation

Put the four DIPs to the upper position to be ON and then start ozone emendation.

1) The digit displayed on the upper left of the LCD indicates the demarcation point that is right now being
     emended.

     Display range: 01, 02, 03, 04, 05, 06, 07, 08, 09, 10

2)  The digit displayed on the upper right of the LCD indicates the ozone measurement at the current demarcation point.

     Display range: Y1, Y2, Y3, Y4, Y5, Y6, Y7, Y8, Y9, Y10

3)  The digit displayed on the bottom line corresponds to the A/D transition level of X axial.

4)  The non-twinkling figure indicates the real-time ozone measurement detected by the sensor.

    5)  The twinkling figure indicates the demarcation point that needs to be set

      Display range: X1, X2, X3, X4, X5, X6, X7, X8, X9, X10

Summary of Contents for O3TH

Page 1: ...Features Real time detection of ambient ozone gas level Full time indicate O3 level Wall mount with LCD display Temperature humidity detection The on off output for control a fan O3 generator or an a...

Page 2: ...t off power first Simualtaneously depress the 2 clips on either of the sides of the detector gently with your nails or other unsharp tools then move off the face part 2 Mount the detector on the place...

Page 3: ...range is 10 1000ppb accuracy 1ppb and setting range is 40 1000ppb its maximum measurement limited is 2000ppb 3 Turn on Turn on the monitor by press power for 2 seconds Temperature measurement displays...

Page 4: ...p on press switch key for about 20 seconds until X10 symbol disappearing It indicates the zero has no any calibration it s still 0 Note Auto zero calibration can be done only when ozone measurement is...

Page 5: ...tion 1 9600bps 2 14400bps 3 3 19200bps 4 28800bps 5 38400bps RESET Put the DIP1 to ON and press switch key for about 25 seconds until the detector is off then all the setting return to the default Ann...

Page 6: ...is finished 6 Now go to demarcation point 2 put the controller in sample gas 7 Write down the un twinkling point of X2 and Y2 8 Press switch to the second demarcation point N 2 9 Press tangent down o...

Page 7: ...key for about 25 seconds until the monitor is off then all the settings return to the default If warm up time is less than 3 months before leaving factory then do emendation as the second row of the...

Page 8: ...ent Controller Placement The Ozone Detector has been designed to measure the ambient concentration of ozone The controller must not be placed directly in an ozone stream For indoor local area monitori...