   Automatikprodukter

Ozone Detector c/w
Indicator for Temperature/Humidity

O3TH

   Dec.11

8

.

When DIP4 is set to OFF(details see below Parameter Setup):

The relay will turn on when O3 measurement < 

O3

 

setting with ON symbol appearing on the right of LCD.

When O3 measurement <O3 setting , the relay will turn off with ON disappearing.

When DIP4 is set to ON(details see below Parameter Setup):

The relay will turn on when O3 measurement > 

O3

 

setting with ON symbol appearing on the right of LCD. When O3

measurement < O3 setting , the relay will turn off with ON disappearing.

The differential of ozone setting, please refer to Parameter Setup.

9

.

The scale bards on the right of LCD indicates the analog output. It is un-effective to this model.

10

.

Calibration of the zero of ozone sensor: after using the ozone sensor for more than one year, the sensor need to be
calibrated again.

Put the monitor into the space of zero ozone and preheating it, press switch key for about  20 seconds until

 X10

symbol appearing on the right of ozone number, then loosen switch key, the monitor starts auto zero calibration.

After 210 seconds until 

X10

 symbol disappearing, it indicates the zero calibration finished.

Cancel the zero calibration: press switch key for about 20 seconds until 

X10 

symbol appearing and then keep on

press switch key for about 20 seconds until 

X10 

symbol disappearing.

It indicates the zero has no any calibration, it’s still 0.

Note: Auto zero calibration can be done only when ozone measurement is above 5ppb.

And keep the controller in the zero ozone environment before 

X10

 symbol disappears.

Parameter Setup ( Service Manual 

V.O3_210

)

Cut off power and simultaneously depress the 2 clips on either of the sides of the monitor gently with your nails or other

        unship tools.

Move the face cover, there is a set of 4 Dipswitches on the right of the circuit board.

        DIP1

ON  -  set  parameter

OFF-  normal  use

Leaving factory: OFF

        DIP2

ON - Fahrenheit

OFF-  Celsius

Leaving factory: OFF

        DIP3

Un-effective for the model

Leaving factory: OFF

        DIP4                     ON- For decrease ozone (to control ventilation system)

                                      OFF- For increase ozone (to control an ozone generator)                          Leaving factory: OFF

__________________________________________________________________________________________________

        Please put DIP1 to ON

, press power key to turn it on, and set the following parameters.

        Press switch for switching parameters, ( tangent down,tangent up) for adjusting values.

        LCD Display

Parameter

Setting Range

Default

-00

Temperature modification

+/-3.0C

0.0C

-01

Humidity modification

+/-9%RH

0

-02

Ozone value correction

+/-30ppb

0.0

-03

Warm up time of the ozone detector

1 - 900sec

300

( no output use, neither 0-10vdc nor

                                                 on/off, is recommended before ozone

measurement becomes stable or

warm up is finished)

-04

Un-effective for the model

0.0

Summary of Contents for O3TH

Page 1: ...Features Real time detection of ambient ozone gas level Full time indicate O3 level Wall mount with LCD display Temperature humidity detection The on off output for control a fan O3 generator or an a...

Page 2: ...t off power first Simualtaneously depress the 2 clips on either of the sides of the detector gently with your nails or other unsharp tools then move off the face part 2 Mount the detector on the place...

Page 3: ...range is 10 1000ppb accuracy 1ppb and setting range is 40 1000ppb its maximum measurement limited is 2000ppb 3 Turn on Turn on the monitor by press power for 2 seconds Temperature measurement displays...

Page 4: ...p on press switch key for about 20 seconds until X10 symbol disappearing It indicates the zero has no any calibration it s still 0 Note Auto zero calibration can be done only when ozone measurement is...

Page 5: ...tion 1 9600bps 2 14400bps 3 3 19200bps 4 28800bps 5 38400bps RESET Put the DIP1 to ON and press switch key for about 25 seconds until the detector is off then all the setting return to the default Ann...

Page 6: ...is finished 6 Now go to demarcation point 2 put the controller in sample gas 7 Write down the un twinkling point of X2 and Y2 8 Press switch to the second demarcation point N 2 9 Press tangent down o...

Page 7: ...key for about 25 seconds until the monitor is off then all the settings return to the default If warm up time is less than 3 months before leaving factory then do emendation as the second row of the...

Page 8: ...ent Controller Placement The Ozone Detector has been designed to measure the ambient concentration of ozone The controller must not be placed directly in an ozone stream For indoor local area monitori...