Ammonia Detector - Manual

NH3/ENH3

April.10

    Automatikprodukter

Electrochemical Transmitter

3

Installation

Note:

Electronics can be destroyed by static electricity.
Therefore, do not touch the equipment without a wrist strap connected to ground or without standing on a conductive
floor.

3.1

Mounting instructions

The specific weight of carbon monoxide is 

lower than that of air (factor 0.59).

 Installation at the 

highest point possible with a distance of cirka 300mm to the ceiling.

Select the location of the sensor according to local regulations.

Consider the ventilation conditions!

Do not mount the transmitter in the center of the airflow (air passages, suction holes)

Mount the transmitter at a location with minimum vibration and minimum variation in temperature (avoid direct

sunlight).

Avoid locations where water, oil etc. may influence proper operation and where mechanical damage might be

possible.

•      

Provide adequate space around the sensor for maintenance and calibration work.

           Duct mounting

    Mount only in a straight section of duct with minimum air vortex.

      Keep a minimum distance of 1 m (3,5 feet) from any curve or obstacle.

•      

Mount only in a duct system with a 

maximum air velocity of 10 m/s

 (2000 ft/min) or less.

•      

Mounting must be performed so that the airflow is in line with probe openings.

3.2

Installation

Open cover of enclosure.

Unplug basic PCB from terminal blocks.

Fix bottom part by screws vertically to the wall (terminal blocks to the ground).

Plug in the basic PCB at X4 and X5.

Replace the cover.

4

Electrical Connection

Instruction

Consider static electricity! See 3.  Mounting

Installation of the electrical wiring should only be performed by a trained specialist according to the connection

diagram, without any power applied to conductors and according to the corresponding regulations!

Avoid any influence of external interference by using a shielded cable.

Recommended cable: J-Y(St)Y 2x2x0.8LG (18 AWG), maximum resistance 73 

Ω

/1000 m (20.8 

Ω

/1000 ft)

When the PCB is mounted, it is important to ensure that the wire shields or any bare wires do not short the

 PCB.

Summary of Contents for ENH3

Page 1: ...ulation of Control Voltage 5 3 CalibrationwithGCD 05ServiceTool 5 4 CalibrationwithGCD 05ConfigurationandCalibrationSoftware 5 5 Addressing only for GCD 05_Bus Mode 5 6 Option relay output 6 Inspectio...

Page 2: ...the gas controller The cable topology for the RS 485 bus can be taken from the Guidelines for wiring and commissioning of the GCD 05 hardware The two control modes are available in parallel 2 2 Sensor...

Page 3: ...sensor for maintenance and calibration work Duct mounting Mount only in a straight section of duct with minimum air vortex Keep a minimum distance of 1 m 3 5 feet from any curve or obstacle Mount onl...

Page 4: ...ures for test gas bottles according to TRGS 220 NH3 calibration gas is toxic never inhale the gas Symptoms at high concentrations Loss of motility and consciousness Procedure if exposed Get the victim...

Page 5: ...t starting point 0 60 mV at starting point 20 before calibration there is no correction of the measuring signal The sensor has to be replaced Remove calibration adapter carefully by turning lightly In...

Page 6: ...the sensor has to be replaced Further information can be taken from the user manual of the GCD 05 Service Tool 5 4 Calibration with GCD 05 Configuration and Calibration Software Connect the PC via USB...

Page 7: ...ss 0 inactive inactive inactive inactive 1 01 16 31 46 2 02 17 32 47 3 03 18 33 48 4 04 19 34 49 5 05 20 35 50 6 06 21 36 51 7 07 22 37 52 8 08 23 38 53 9 09 24 39 54 A 10 25 40 55 B 11 26 41 56 C 12...

Page 8: ...ment out of original packing Plug in sensor element into the PCB at X3 Plug in carefully the PCB into terminal block X4 X5 Calibrate according to section 5 7 Troubleshooting 7 1 Analog Mode Trouble Ca...

Page 9: ...munication at the transmitter Transmitter not addressed check bus wiring incl topology and termination Voltage 16 V ____________________________________________________________________________________...

Page 10: ...Hydrogen H2 200 ppm 0 ppm Sulphur dioxide SO2 20 ppm 7 ppm Hydrogen sulphide H2S 20 ppm 7 ppm Nitrate monoxide NO 20 ppm 1 ppm Nitrogen dioxide NO2 20 ppm 20 ppm Chlorine Cl2 20 ppm 55 ppm Carbon dio...

Page 11: ...d Cableentry Standard 1 x M 20 Wireconnection Screw type terminal min 0 25 max 2 5 mm2 Wire distance Current signal ca 500 mVoltage signal ca 200 m Guidelines EMC Directive 89 336 EEG CE Warranty 1 ye...

Page 12: ...ection Diagram Two wire connection by 4 20mA without option Three wire connection Vdc outputsignal 0 20mA output signal Relay output LCD display Heating Connection field bus and tension GCD Gas Contro...

Page 13: ...T ool R1 X5 Zero Option Relay Anal Output VDC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Option Manual Calibration Option Manual Addressing Position 4 3 2 1 5 4 3 2 1 1 2 3 4 5 6 7...

Page 14: ...miliar with proper installation techniques and with codes standards and proper safety procedures for control installations and the latest edition of the National Electrical Code ANSI NFPA70 It is also...

Reviews: