Ammonia Detector - Manual

NH3/ENH3

April.10

    Automatikprodukter

Electrochemical Transmitter

5.5

Addressing, only for GCD-05_Bus Mode

In the GCD-05_Bus mode each transmitter gets its communication address.

In the standard version with the communication connector X12, addressing is done by means of the GCD-05 Service
Tool or by the GCD-05 Configuration and Calibration Software.

See user manual of the Service Tool or of the Configuration and Calibration Software.

In the manual addressing version which can be identified by the address switch being equipped, there is a maximum
of 60 addresses to be selected. See fig. 3.

The jumper is responsible to define the address group and the switch to define the address according to the following
table

Switch              Jumper pos. 01      Jumper pos. 02    Jumper pos. 03

Jumper pos. 04

position

=  address

= address

= address

= address

0

inactive

inactive

inactive

inactive

1

01

16

31

46

2

02

17

32

47

3

03

18

33

48

4

04

19

34

49

5

05

20

35

50

6

06

21

36

51

7

07

22

37

52

8

08

23

38

53

9

09

24

39

54

A

10

25

40

55

B

11

26

41

56

C

12

27

42

57

D

13

28

43

58

E

14

29

44

59

F

15

30

45

60

5.6

Option Relay Output

The two relays are activated in dependence of the gas concentration. If the gas concentration exceeds the adjusted
alarm threshold, the corresponding relay switches on.

If the gas concentration falls below the threshold minus hysteresis, the relay switches off again.

The contact function for relay 2, NC (normally closed) or NO (normally open), can be selected via the jumper NO/
NC. See fig 1 and 3. Relay 1 is equipped with a change-over contact.

Via the ModBus interface the two alarm thresholds and the hysteresis are freely adjustable at the PC within the
measuring range.

The procedure can be read from the user manual ”ModBus Software”.

The following parameters are factory-set.

Alarm threshold 1 = Relay 1:

80 ppm

Alarm threshold 2 = Relay 2:

250 ppm

Switching  hysteresis:

 15 ppm

Summary of Contents for ENH3

Page 1: ...ulation of Control Voltage 5 3 CalibrationwithGCD 05ServiceTool 5 4 CalibrationwithGCD 05ConfigurationandCalibrationSoftware 5 5 Addressing only for GCD 05_Bus Mode 5 6 Option relay output 6 Inspectio...

Page 2: ...the gas controller The cable topology for the RS 485 bus can be taken from the Guidelines for wiring and commissioning of the GCD 05 hardware The two control modes are available in parallel 2 2 Sensor...

Page 3: ...sensor for maintenance and calibration work Duct mounting Mount only in a straight section of duct with minimum air vortex Keep a minimum distance of 1 m 3 5 feet from any curve or obstacle Mount onl...

Page 4: ...ures for test gas bottles according to TRGS 220 NH3 calibration gas is toxic never inhale the gas Symptoms at high concentrations Loss of motility and consciousness Procedure if exposed Get the victim...

Page 5: ...t starting point 0 60 mV at starting point 20 before calibration there is no correction of the measuring signal The sensor has to be replaced Remove calibration adapter carefully by turning lightly In...

Page 6: ...the sensor has to be replaced Further information can be taken from the user manual of the GCD 05 Service Tool 5 4 Calibration with GCD 05 Configuration and Calibration Software Connect the PC via USB...

Page 7: ...ss 0 inactive inactive inactive inactive 1 01 16 31 46 2 02 17 32 47 3 03 18 33 48 4 04 19 34 49 5 05 20 35 50 6 06 21 36 51 7 07 22 37 52 8 08 23 38 53 9 09 24 39 54 A 10 25 40 55 B 11 26 41 56 C 12...

Page 8: ...ment out of original packing Plug in sensor element into the PCB at X3 Plug in carefully the PCB into terminal block X4 X5 Calibrate according to section 5 7 Troubleshooting 7 1 Analog Mode Trouble Ca...

Page 9: ...munication at the transmitter Transmitter not addressed check bus wiring incl topology and termination Voltage 16 V ____________________________________________________________________________________...

Page 10: ...Hydrogen H2 200 ppm 0 ppm Sulphur dioxide SO2 20 ppm 7 ppm Hydrogen sulphide H2S 20 ppm 7 ppm Nitrate monoxide NO 20 ppm 1 ppm Nitrogen dioxide NO2 20 ppm 20 ppm Chlorine Cl2 20 ppm 55 ppm Carbon dio...

Page 11: ...d Cableentry Standard 1 x M 20 Wireconnection Screw type terminal min 0 25 max 2 5 mm2 Wire distance Current signal ca 500 mVoltage signal ca 200 m Guidelines EMC Directive 89 336 EEG CE Warranty 1 ye...

Page 12: ...ection Diagram Two wire connection by 4 20mA without option Three wire connection Vdc outputsignal 0 20mA output signal Relay output LCD display Heating Connection field bus and tension GCD Gas Contro...

Page 13: ...T ool R1 X5 Zero Option Relay Anal Output VDC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Option Manual Calibration Option Manual Addressing Position 4 3 2 1 5 4 3 2 1 1 2 3 4 5 6 7...

Page 14: ...miliar with proper installation techniques and with codes standards and proper safety procedures for control installations and the latest edition of the National Electrical Code ANSI NFPA70 It is also...

Reviews: