Ammonia detector - Manual

NH3/ENH3

    

April.10

Electrochemical Transmitter

9

Technical Data

General sensor performances

Gas type

Ammonia (NH3)

Sensor element

Electrochemical, diffusion

Measuring range

0 - 300 ppm / 0 - 1000 ppm

Pressure range

Atmosphere ± 15 %

Humidity

15 – 90 % RH non condensing

Storage temperature range

5 °C to 20 °C

Storage  time

Max. 3 months

_____________________________________________________________________________

Type NH3

Accuracy

4 ppm

Repeatability

< 3 % of reading

Zero-point

0 ppm ± 16 ppm

Long-term output drift

< 5% signal loss/6 months

Response time

t

90

 < 35 sec.

Temperature range

-10 °C to + 40 °C

Life expectancy

> 2 years/normal operating environment

Cross sensitivity*

Concentration

Reaction

  Carbon monoxide; CO                            300 ppm

0 ppm

  Hydrogen H2

200 ppm

0 ppm

  Sulphur dioxide SO2                                 20 ppm

- 7 ppm

  Hydrogen sulphide H2S

20 ppm

7 ppm

  Nitrate monoxide NO

20 ppm

- 1 ppm

  Nitrogen dioxide NO2

20 ppm

- 20 ppm

  Chlorine Cl2

20 ppm

- 55 ppm

  Carbon dioxide CO2

  2 % vol

0 ppm

_____________________________________________________________________________

Type ENH3

Accuracy

< 15 ppm

Repeatability

< 5 % of reading

Zero-point

0 ppm ± 15 ppm

Long-term sensitivity output drift

< 10% signal loss/6 months

Response time

t

90

 < 120 sec.; t50 < 20 sec.

Temperature range

-40 °C to + 10 °C

Life expectancy

> 18 months/normal operating environment

Cross sensitivity*

Concentration

Reaction

  Carbon monoxide; CO

  100 ppm

95 ppm

  Hydrogen H2

3000 ppm

                               3000 ppm

  Sulphur dioxide SO2

      20 ppm

    5 ppm

  Hydrogen sulphide H2S

     20 ppm

                                    40 ppm

  Phosphates

   300 ppm

    0 ppm

  Nitrogen dioxide NO2

     10 ppm

                                      0 ppm

  Chlorine Cl2

       5 ppm

                                      0 ppm

  Hydrogen chloride HCl

      10 ppm

    0 ppm

  Carbon dioxide CO2

  0,5 % vol

                                      0 ppm

  Alcohols

1000 ppm

                                         yes

  Amine                                                             —-

       yes

  Arsines

   0,2 ppm

                                      0 ppm

Summary of Contents for ENH3

Page 1: ...ulation of Control Voltage 5 3 CalibrationwithGCD 05ServiceTool 5 4 CalibrationwithGCD 05ConfigurationandCalibrationSoftware 5 5 Addressing only for GCD 05_Bus Mode 5 6 Option relay output 6 Inspectio...

Page 2: ...the gas controller The cable topology for the RS 485 bus can be taken from the Guidelines for wiring and commissioning of the GCD 05 hardware The two control modes are available in parallel 2 2 Sensor...

Page 3: ...sensor for maintenance and calibration work Duct mounting Mount only in a straight section of duct with minimum air vortex Keep a minimum distance of 1 m 3 5 feet from any curve or obstacle Mount onl...

Page 4: ...ures for test gas bottles according to TRGS 220 NH3 calibration gas is toxic never inhale the gas Symptoms at high concentrations Loss of motility and consciousness Procedure if exposed Get the victim...

Page 5: ...t starting point 0 60 mV at starting point 20 before calibration there is no correction of the measuring signal The sensor has to be replaced Remove calibration adapter carefully by turning lightly In...

Page 6: ...the sensor has to be replaced Further information can be taken from the user manual of the GCD 05 Service Tool 5 4 Calibration with GCD 05 Configuration and Calibration Software Connect the PC via USB...

Page 7: ...ss 0 inactive inactive inactive inactive 1 01 16 31 46 2 02 17 32 47 3 03 18 33 48 4 04 19 34 49 5 05 20 35 50 6 06 21 36 51 7 07 22 37 52 8 08 23 38 53 9 09 24 39 54 A 10 25 40 55 B 11 26 41 56 C 12...

Page 8: ...ment out of original packing Plug in sensor element into the PCB at X3 Plug in carefully the PCB into terminal block X4 X5 Calibrate according to section 5 7 Troubleshooting 7 1 Analog Mode Trouble Ca...

Page 9: ...munication at the transmitter Transmitter not addressed check bus wiring incl topology and termination Voltage 16 V ____________________________________________________________________________________...

Page 10: ...Hydrogen H2 200 ppm 0 ppm Sulphur dioxide SO2 20 ppm 7 ppm Hydrogen sulphide H2S 20 ppm 7 ppm Nitrate monoxide NO 20 ppm 1 ppm Nitrogen dioxide NO2 20 ppm 20 ppm Chlorine Cl2 20 ppm 55 ppm Carbon dio...

Page 11: ...d Cableentry Standard 1 x M 20 Wireconnection Screw type terminal min 0 25 max 2 5 mm2 Wire distance Current signal ca 500 mVoltage signal ca 200 m Guidelines EMC Directive 89 336 EEG CE Warranty 1 ye...

Page 12: ...ection Diagram Two wire connection by 4 20mA without option Three wire connection Vdc outputsignal 0 20mA output signal Relay output LCD display Heating Connection field bus and tension GCD Gas Contro...

Page 13: ...T ool R1 X5 Zero Option Relay Anal Output VDC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Option Manual Calibration Option Manual Addressing Position 4 3 2 1 5 4 3 2 1 1 2 3 4 5 6 7...

Page 14: ...miliar with proper installation techniques and with codes standards and proper safety procedures for control installations and the latest edition of the National Electrical Code ANSI NFPA70 It is also...

Reviews: