   Automatikprodukter

Ammonia detector - Manual

NH3/ENH3

    

April.10

Electrochemical Transmitter

4.1

Wiring connection

Unscrew cover of enclosure.

Unplug basic PCB from terminal blocks.

Connect cable leads to terminal block X4.

Plug the PCB in the fixed terminal blocks on base.

Screw cover on base

5 Commissioning

            Consider commisioning instructions at any exchange of sensor elements.

   Only trained technicians should perform the following:

Check mounting location.

Select output signal form: Current or voltage, and starting point 0 o 20%. See fig.4

Check supply voltage.

Check PCB  for proper mounting at X4 and X5.

Check for correct sensor element at terminal X3 PCB EC-S.

Addressing of the transmitter in the GCD-05_Bus mode..

Calibration of the transmitter (if not factory-calibrated).

   

Note:

Prior to calibration the sensor element must be fully stabilized by applying power voltage for at least 18 hours
without interruption.

          Please observe proper handling procedures for test gas bottles according to TRGS 220!

NH

3

 calibration gas is toxic, never inhale the gas!

Symptoms at high concentrations: Loss of motility and consciousness.

Procedure if exposed: Get the victim into fresh air at once, consult doctor.

5.1

Calibration

Depending on the version and the control mode there are three different possibilities to calibrate the transmitter:

Manual calibration

Manual calibration is only possible if the transmitter is equipped with the push-button ”Zero” and the potentiometer
”Gain” (= version for manual calibration).

Manual calibration is possible both in analog mode and in DGC-05_Bus mode.

In the GCD-05_Bus mode the jumper V-A has to be set before manual calibration.

Only by doing so the control voltage is available at the test pins X6.

Remove the jumper after calibration

Calibration with the Service Tool DGC-05

In the standard version (equipped with the communication connector X12) the transmitter is delivered for tool and/
or software calibration.

In the analog mode the service tool calibration is only possible with the 3-wire technique of the transmitter!

In the GCD-05_Bus mode calibration is always possible.

Summary of Contents for ENH3

Page 1: ...ulation of Control Voltage 5 3 CalibrationwithGCD 05ServiceTool 5 4 CalibrationwithGCD 05ConfigurationandCalibrationSoftware 5 5 Addressing only for GCD 05_Bus Mode 5 6 Option relay output 6 Inspectio...

Page 2: ...the gas controller The cable topology for the RS 485 bus can be taken from the Guidelines for wiring and commissioning of the GCD 05 hardware The two control modes are available in parallel 2 2 Sensor...

Page 3: ...sensor for maintenance and calibration work Duct mounting Mount only in a straight section of duct with minimum air vortex Keep a minimum distance of 1 m 3 5 feet from any curve or obstacle Mount onl...

Page 4: ...ures for test gas bottles according to TRGS 220 NH3 calibration gas is toxic never inhale the gas Symptoms at high concentrations Loss of motility and consciousness Procedure if exposed Get the victim...

Page 5: ...t starting point 0 60 mV at starting point 20 before calibration there is no correction of the measuring signal The sensor has to be replaced Remove calibration adapter carefully by turning lightly In...

Page 6: ...the sensor has to be replaced Further information can be taken from the user manual of the GCD 05 Service Tool 5 4 Calibration with GCD 05 Configuration and Calibration Software Connect the PC via USB...

Page 7: ...ss 0 inactive inactive inactive inactive 1 01 16 31 46 2 02 17 32 47 3 03 18 33 48 4 04 19 34 49 5 05 20 35 50 6 06 21 36 51 7 07 22 37 52 8 08 23 38 53 9 09 24 39 54 A 10 25 40 55 B 11 26 41 56 C 12...

Page 8: ...ment out of original packing Plug in sensor element into the PCB at X3 Plug in carefully the PCB into terminal block X4 X5 Calibrate according to section 5 7 Troubleshooting 7 1 Analog Mode Trouble Ca...

Page 9: ...munication at the transmitter Transmitter not addressed check bus wiring incl topology and termination Voltage 16 V ____________________________________________________________________________________...

Page 10: ...Hydrogen H2 200 ppm 0 ppm Sulphur dioxide SO2 20 ppm 7 ppm Hydrogen sulphide H2S 20 ppm 7 ppm Nitrate monoxide NO 20 ppm 1 ppm Nitrogen dioxide NO2 20 ppm 20 ppm Chlorine Cl2 20 ppm 55 ppm Carbon dio...

Page 11: ...d Cableentry Standard 1 x M 20 Wireconnection Screw type terminal min 0 25 max 2 5 mm2 Wire distance Current signal ca 500 mVoltage signal ca 200 m Guidelines EMC Directive 89 336 EEG CE Warranty 1 ye...

Page 12: ...ection Diagram Two wire connection by 4 20mA without option Three wire connection Vdc outputsignal 0 20mA output signal Relay output LCD display Heating Connection field bus and tension GCD Gas Contro...

Page 13: ...T ool R1 X5 Zero Option Relay Anal Output VDC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Option Manual Calibration Option Manual Addressing Position 4 3 2 1 5 4 3 2 1 1 2 3 4 5 6 7...

Page 14: ...miliar with proper installation techniques and with codes standards and proper safety procedures for control installations and the latest edition of the National Electrical Code ANSI NFPA70 It is also...

Reviews: