-BL287*B02F*CC20  11/16-

LINK does not flash

Remedy

Check the connection of this unit.

Check conditions of the master unit 

and slave unit.

Disconnect this unit once, and then reconnect it.

[Troubleshooting]

Things to be checked

Remedy

Things to be checked

Remedy

Things to be checked

Remedy

Things to be checked

Remedy

Things to be checked

1)  If LINK on the master unit is flashing and LINK on the slave unit is lit, it is possible that the master 

unit has a fault or power supply (24V-0V) is directly connected to the DP-DN pins of the slave unit.

*

 If LINK is lit while ALM is flashing, it means a failure in single unit simplified replacement. 

2)  If LINK on the master unit is flashing and LINK on the slave unit is unlit, it is possible that the power 

(24V DC) is not supplied to the master unit, there is a disconnection on the transmission line (DP, 
DN), or the slave unit has been damaged. 

3)  If LINK on the master unit is not flashing, check the power supply to the master unit. Also, since there 

is a possibility that some system error has occurred, refer to the user’s manual of the master unit.

4)  A slave unit incompatible with Ver.1.1 cannot be used in connection to the AnyWireASLINK system 

for word transmission. Check the setting of the master unit, and lot No. of the slave unit. 

ALM is lit

ALM is flashing

LINK and ALM flashes alternately

LINK is lit and ALM is flashing: Model mismatching error (Failure in single unit simplified replacement)

Check the connection of I/O terminals 

on the slave unit.

Adjust the voltage of external power supply connected to the I/O side of the slave unit so that it falls 
within the rating (21.6 to 27.6V).
In addition, ensure that there is no contact between and erroneous wiring of transmission lines.

Adjust the voltage of external power supply to the master unit so that it will be in the range from 21.6 to 
27.6V. (Recommended voltage is 26.4V.) Check the total length.
Review the total length and wire diameter of transmission line so that the load will not exceed the current 
limit supplied by the transmission line and adjust the connected load. (In the case of the wire size of 
1.25mm

2

 and total length of 50m or less, the current supplied by the transmission line is 2A.)

*

 If ALM is flashing while LINK is lit, it means a failure in single unit simplified replacement. 

Check if the replacement slave unit is of the same type as that of the slave unit before the replacement.

Check if the function version for the replacement slave unit is older than that of the slave unit before the 
replacement.

*

 If the function version of the replacement slave unit is older, the single unit simplified replacement 

function does not work.

The address of the slave unit is either unregistered or duplicated.
Take the following actions. 

*

 The slave unit cannot be used with the factory-set address.

1)  Set an address correctly.
2)  Check if there is a slave unit on which the indicator lamps are flashing in the same manner and reset 

the addresses so that they are not duplicated.

Check the address of the slave unit.

Check the address of the slave unit.

Check the model of the slave unit.

Check the lot No. of the slave unit.

Check the connection of the slave 

unit.

Check the voltage (24V DC) of 

external power supply to the master 

unit.

Check if the address of the replacement slave unit is the same as the address before shipment (a bit 
address of 511).

*

 If the address of the replacement slave unit is not the same as the address before shipment, the single 

unit simplified replacement function does not work.

Defective connections and the like may have caused single unit simplified replacement to fail.
Remove the slave unit after replacement, and make connections again.

*

When two or more replacement slave units are simultaneously connected, the single unit simplified 

replacement function does not work.

Summary of Contents for BL287PB-02F-CC20

Page 1: ...a potentially hazardous situation which if not handled correctly may result in personal injury or property damage CAUTION WARNING System power supply Use a stable 24V DC power supply Use of an unstab...

Page 2: ...Lot No About Word Transmission 3 Some products have no indication of function version Year Numbers Lower two digits of the Christian era Month Alphabet as per the table below 19E means May 2019 Singl...

Page 3: ...fied replacement function see the lot No and the manual for the slave unit When a slave unit of a new function version is replaced with that of an old function version the single unit simplified repla...

Page 4: ...s PNP input 1 point output 1 point Function 4 This terminal can be used in connection to the AnyWireASLINK unit for word transmission Note that this terminal cannot handle word data by setting a word...

Page 5: ...Connect AnyWireASLINK AnyWireASLINK terminator One terminator should be connected to the DP DN terminal farthest from the AnyWireASLINK master unit Connect it correctly so as not to set the wrong pol...

Page 6: ...of crosstalk caused by transmitted signals and stabilize signals The above filters must be inserted regardless of whether power is supplied to all terminals collectively from the power supply for the...

Page 7: ...all the DP DN 24V and 0V lines run in parallel is more than 50m 24V DC stabilized power supply General purpose power supply filter Use it if necessary 2 wire terminal 2 wire terminal 4 wire terminal 2...

Page 8: ...dicator Red Brown 24V Black IN Blue 0V Input PNP Black OUT0 Blue 0V NPN Brown 24V Black OUT0 Black OUT1 Blue 0V Brown 24V Black OUT1 PNP Black OUT Blue 0V NPN Brown 24V Black OUT Output Input output m...

Page 9: ...e address number within the range of bit address 0 to 254 For the input output mixed type the same address number should be assigned to both input and output Set the address number so that the area oc...

Page 10: ...lified replacement function fails This operation occurs on the S W version B or later version 3 If ID duplication is detected when the master unit executes automatic address recognition this indicatio...

Page 11: ...t will be in the range from 21 6 to 27 6V Recommended voltage is 26 4V Check the total length Review the total length and wire diameter of transmission line so that the load will not exceed the curren...

Page 12: ...e output device will be damaged To connect loads e g I O ports that are controlled with a power supply other than the one used for the AnyWireASLINK system always use a 4 wire isolated terminal Otherw...

Page 13: ...circuited the output device will be damaged To connect loads e g I O ports that are controlled with a power supply other than the one used for the AnyWireASLINK system always use a 4 wire isolated ter...

Page 14: ...of conductive substances in the environment where the device is used Pollution level 2 means the occurrence of only pollution by non conductive substances In such an environment however electrical co...

Page 15: ...ADP 87 Mounting adaptor 23 2 4 2 4 80 8 20 2 n 1 40 2 4 4 2 6 15 2 3 5 20 2 11 5 5 R 1 2 1 5 1 7 7 5 3 5 BL287 B02F CC20 15 16 Connection hook Connection hook...

Page 16: ...ted in Japan 2013 2014 2017 2018 2019 2020 UMA 08833AM EN Anywire Corporation Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Contact by mail Contact info_e anywire jp Contact by website...

Reviews: