background image

-B281*B02U*CC20  12/17-

LINK does not flash

Remedy

Check the connection of this unit.

Check conditions of the master unit 

and slave unit.

Disconnect this unit once, and then reconnect it.

[Troubleshooting]

Things to be checked

Remedy

Things to be checked

Remedy

Things to be checked

Remedy

Things to be checked

Remedy

Things to be checked

1)  If LINK on the master unit is flashing and LINK on the slave unit is lit, it is possible that the master 

unit has a fault or power supply (24V-0V) is directly connected to the DP-DN pins of the slave unit.

*

 If LINK is lit while ALM is flashing, it means a failure in single unit simplified replacement. 

2)  If LINK on the master unit is flashing and LINK on the slave unit is unlit, it is possible that the power 

(24V DC) is not supplied to the master unit, there is a disconnection on the transmission line (DP, 
DN), or the slave unit has been damaged. 

3)  If LINK on the master unit is not flashing, check the power supply to the master unit. Also, since there 

is a possibility that some system error has occurred, refer to the user’s manual of the master unit.

4)  A slave unit incompatible with Ver.1.1 cannot be used in connection to the AnyWireASLINK system 

for word transmission. Check the setting of the master unit, and lot No. of the slave unit. 

ALM is lit

ALM is flashing

LINK and ALM flashes alternately

LINK is lit and ALM is flashing: Model mismatching error (Failure in single unit simplified replacement)

Check the connection of I/O terminals 

on the slave unit.

When IN flashes in synchronization with LINK while ALM is lit, the unit has I/O disconnection.
If only ALM is lit, the unit has I/O short-circuit or I/O voltage drop.
1)  Make sure that the slave unit I/O line and load are normally connected. Use caution about 

disconnection of the wiring and insufficient screw tightening.

2)  To connect a mechanical contact (relay, switch, etc.) as load, OFF signal cannot be differentiated 

from disconnection. In this case, set the equipment parameter for the disconnection detecting 
function to OFF.

3)  Check wiring of the slave unit terminals to ensure that the connected load meets the power supply 

and output specifications of ASLINER, and adjust it as required. 

4)  Adjust the power supply voltage of an external power source connected to the slave unit I/O line, so 

that the power supply voltage does not exceed the rated voltage range (21.6V to 27.6V). Make sure 
that wires of the transmission line do not touch each other. Check for incorrect wiring of the terminals.

Adjust the voltage of external power supply to the master unit so that it will be in the range from 21.6 to 
27.6V. (Recommended voltage is 26.4V.) Check the total length.
Review the total length and wire diameter of transmission line so that the load will not exceed the current 
limit supplied by the transmission line and adjust the connected load. (In the case of the wire size of 
1.25mm

2

 and total length of 50m or less, the current supplied by the transmission line is 2A.)

*

 If ALM is flashing while LINK is lit, it means a failure in single unit simplified replacement. 

Check if the replacement slave unit is of the same type as that of the slave unit before the replacement.

Check if the function version for the replacement slave unit is older than that of the slave unit before the 
replacement.

*

 If the function version of the replacement slave unit is older, the single unit simplified replacement 

function does not work.

The address of the slave unit is either unregistered or duplicated.
Take the following actions. 

*

 The slave unit cannot be used with the factory-set address.

1)  Set a bit address correctly in a range of 0 to 254.
2)  Check if there is a slave unit on which the indicator lamps are flashing in the same manner and reset 

the addresses so that they are not duplicated.

Check the address of the slave unit.

Check the address of the slave unit.

Check the model of the slave unit.

Check the lot No. of the slave unit.

Check the connection of the slave 

unit.

Check the voltage (24V DC) of 

external power supply to the master 

unit.

Check if the address of the replacement slave unit is the same as the address before shipment (a bit 
address of 511).

*

 If the address of the replacement slave unit is not the same as the address before shipment, the single 

unit simplified replacement function does not work.

Defective connections and the like may have caused single unit simplified replacement to fail.
Remove the slave unit after replacement, and make connections again.

*

 When two or more replacement slave units are simultaneously connected, the single unit simplified 

replacement function does not work.

Summary of Contents for B281-B-02U-CC20 Series

Page 1: ...m safely are indicated as shown below You must observe these precautions Notes on Safety A CAUTION indicates a potentially hazardous situation which if not handled correctly may result in personal inj...

Page 2: ...Lot No About Word Transmission 3 Some products have no indication of function version Year Numbers Lower two digits of the Christian era Month Alphabet as per the table below 19E means May 2019 Single...

Page 3: ...lacement function see the lot No and the manual for the slave unit When a slave unit of a new function version is replaced with that of an old function version the single unit simplified replacement f...

Page 4: ...used in connection to the AnyWireASLINK unit for word transmission Note that this terminal cannot handle word data by setting a word address 5 The single unit simplified replacement function works ev...

Page 5: ...n external power supply How to Connect AnyWireASLINK AnyWireASLINK terminator CAUTION Refer to Table 1 so that the size and length of the transmission line and the allowable supply current lie within...

Page 6: ...resistance suppress the adverse effects of crosstalk caused by transmitted signals and stabilize signals The above filters must be inserted regardless of whether power is supplied to all terminals co...

Page 7: ...all the DP DN 24V and 0V lines run in parallel is more than 50m 24V DC stabilized power supply General purpose power supply filter Use it if necessary 2 wire terminal 2 wire terminal 4 wire terminal 2...

Page 8: ...O connection line I O connection line I O connection line LINK IN0 IN1 ALM Transmission indicator Green Input indicator Orange Input indicator Orange Alarm indicator Red Transmission line connection...

Page 9: ...ay cause a fault of the equipment Black DN Red DP For the power supply to be connected be sure to use a 24V DC stabilized power supply CAUTION AnyWireASLINK master 24V DC Transmission signal Lot No 19...

Page 10: ...t detection are enabled Variable Description Factory setting 0 This parameter is used to specify whether the I O cable disconnection detecting function is enabled or disabled Input When sensor s circu...

Page 11: ...smission signal and power supply are normally connected and the unit is set to the factory set address For S W version A or 3 digit lot No This condition is detected when the master unit executes auto...

Page 12: ...e power supply voltage of an external power source connected to the slave unit I O line so that the power supply voltage does not exceed the rated voltage range 21 6V to 27 6V Make sure that wires of...

Page 13: ...ching current ON current OFF current ON voltage OFF voltage Supply current at 24VL 24V DC 3 5mA 2 2mA or more 1mA or less 16V or more 24VL IN 8V or less 24VL IN 50mA max 24VL 0VL per point 2 wire non...

Page 14: ...mA 2 2mA or more 1mA or less 16V or more IN 0VL 8V or less IN 0VL 50mA max 24VL 0VL per point 2 wire non isolated PNP input B281SB 02US CC20 B281XB 02US CC20 Input To connect inductive load use a surg...

Page 15: ...ution level 2 General specifications 0 55 C 10 90 RH No condensation 25 75 C 10 90 RH No condensation Based on JIS B 3502 and IEC 61131 2 Based on JIS B 3502 and IEC 61131 2 No corrosive gas 0 2000m 2...

Page 16: ...7 5 3 5 5 5 1 5 1 7 R 1 2 23 10 4 3 5 2 4 1 1 2 4 40 2 2 6 15 2 3 5 17 2 10 2 4 4 68 8 17 2 n 1 2 4 B281 B02U CC20 16 17 ADP 81 Mounting adaptor Connection hook Connection hook...

Page 17: ...in Japan 2013 2014 2016 2017 2018 2019 2020 UMA 08717AP EN Anywire Corporation Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Contact by mail Contact info_e anywire jp Contact by websit...

Reviews: