13 (136)
3.2.5
Addressing Modes
As a full EtherCAT, the module supports the following addressing modes:
•
position addressing
•
node addressing
•
logical addressing
3.2.6
Watchdog Functionality
Output I/O Sync Manager Watchdog
If enabled, this watchdog monitors the PDO communication towards the Anybus module. If the
master doesn’t update the Read Process Data within the specified time period, this will trigger a
timeout condition in the module, causing it to shift from OPERATIONAL to SAFE-OPERATION-
AL. The supervision-bit (SUP) is also affected by this.
The sync manager watchdog is enabled by default in the ESI file, with a default time period of
100 ms.
The sync manager watchdog can always be disabled/enabled manually in the configuration tool
for the master.
See also...
•
PDI Watchdog
PD watchdog functionality is not supported.
Anybus
®
CompactCom
™
40 EtherCAT
®
Network Guide
SCM-1202-034 1.1