10. Snug down a first set of three bolts located at the corners of an equilateral triangle (for
example: bolts in positions 1-5-9 of figure 2-5). Fit the gear unit to the drive shaft.
11. Tighten the bolts (following the triangular pattern) in a circular direction, repeating the operation
several times until all bolts are tightened to the correct torque, in accordance with the type of
disk/gear unit shown at the bottom of figure 2-5.
Figure 2-5. Main Drive Installation Information
After making the electrical connections to the motor and completing the cabling installation, check
the direction of rotation by switching the motor on and off very quickly. When the direction is
correct, the upper part of the screen moves upwards. Also check that the insulation resistance of
the motor is above acceptable limits.