Installation examples
2-5-A-C: 1 heating zone and sanitary hot water + low loss header
33
2-5-A-C: 1 heating zone and sanitary hot water + low loss header
Description
•
R600 with low loss header
•
Weather compensated control (E8 or
LOGON B)
•
1 mixed heating zone
•
Sanitary hot water
Tips
•
Complete accessory kits with low loss
header are available for
∆
T=10-20K
(see chapter „Accessories“).
•
The primary circuit should be de-
signed for
∆
T=20K, this guarantees a
high boiler efficiency.
•
When the secundary circuit is de-
signed for a
∆
T smaller than 20K, the
flow temperature in the header will be
lower than the flow temperature of the
boiler. This should be taken in consid-
eration during the design stage.
•
The header should be positioned
close to the boiler, to avoid a negative
influance on the temperature control
quality.
•
In case of a boiler room installed on
the roof, the boiler may never be hy-
draulically connected at the highest
point of the installation.