COMMISSIONING
SECTION 4
Lighting the Burner
Open the main gas supply cock after all connections to the gas control are completed
and using a manometer, test all connections up to the gas control inlet. Purge air from
pipework and ensure there are no loose connections to burner or pilot pipe.
1. Ensure gas supply is on.
2. Turn gas control knob to PILOT position.
3. Depress knob and activate piezo igniter.
4. Keep knob pressed in for a further 40 seconds after pilot lights, then release knob and
check that pilot remains lit. If not, turn off then wait 3 minutes before repeating from
step 2. Observe via the view port.
5. Turn control knob to ON and turn control thermostat dial to required water
temperature. The burner will now light.
6. Check pilot and gas connections for soundness with leak detection fluid whilst burner
is alight. Turn off, seal any leakages, then re-test.
WARNING! if pilot goes out, do not attempt to relight gas until at least 3 minutes
have elapsed.
Shutting Off The Burner
For long periods only, (7 days or more) turn control knob to PILOT, partially depress
knob, then turn clockwise to OFF. Turn off gas service cock. For shorter periods leave
heater under thermostat control.
Checking Incoming Gas Pressure
1. Turn gas control knob clockwise to OFF.
2. Release bleed screw A and connect pressure gauge tube.
3. Light burner as described above.
4. With the main burner running, the incoming gas pressure must be as follows:
PROPANE
37 mbar (14.86 in W.g.)
BUTANE
28 mbar (11.26 in W.g.)
The service governor should be adjusted if necessary to give the above values.
5. Turn the gas control to OFF, remove the pressure gauge, tighten the bleed screw and
check for gas leaks using a leak detection fluid.
HI-FLO RANGE
28
Fig 22.
Summary of Contents for L24/31
Page 3: ......
Page 5: ......
Page 14: ...INSTALLATION SECTION 3 9 Bulk Storage Vessel Installation Cylinder Installation Fig 3 ...
Page 22: ...INSTALLATION SECTION 3 17 Fig 8 Fig 8a ...
Page 24: ...INSTALLATION SECTION 3 WATER CONNECTIONS 19 Fig 10 Fig 11 ...
Page 27: ...INSTALLATION SECTION 3 WATER CONNECTIONS 22 Fig 14 Fig 15 ...
Page 30: ...INSTALLATION SECTION 3 WATER CONNECTIONS 25 Fig 18 Fig 19 ...
Page 51: ...PARTS LIST AND ILLUSTRATIONS SECTION 9 46 Hi Flo Model L32 143 Hi Flo Models L65 169 L81 251 ...
Page 53: ...PARTS LIST AND ILLUSTRATIONS SECTION 9 48 Hi Flo Models L62 309 L54 399 ...
Page 58: ...NOTES 53 ...
Page 59: ...NOTES 54 ...
Page 60: ......