TECHNICAL DATA
SECTION 2
Hi-Flo
RANGE
5
Storage Capacity
l
145
295
386
282
245
gal
32
65
81
62
54
Recovery thro' 44ºC/80ºF
l/h
649
788
1140
1403
1821
gal/h
143
169
251
309
399
Recovery thro' 56ºC/100ºF
l/h
517
613
913
1122
1449
gal/h
114
135
201
247
319
Recovery thro' 72ºC/130ºF
l/h
399
472
699
862
1117
gal/h
88
104
154
190
246
Heat Input Gross
kW
41.8
49
76
92.5
122
Btu/h
142.622 167,188 259,312 315,610 416,264
Heat Input Net
kW
38
44
69
84
111
Btu/h
129,656 150,128 235,428 286,608 378,732
Gas
LPG CAT I
3
mbar
37
37
37
37
37
Inlet Gas Pressure
ins wg.
14.86
14.86
14.86
14.86
14.86
mbar
28
28
28
28
28
ins wg.
11.26
11.26
11.26
11.26
11.26
Gas Flow Rate Propane
m
3
/h
1.61
1.89
2.93
3.58
4.71
ft
3
/h
57
66.87
103.7
126.25 166.50
Gas Flow Rate Butane
m
3
/h
1.26
1.48
2.29
2.79
3.68
ft
3
/h
44.6
52.24
81.04
98.63
130.08
Gas Connection
Rc (in BSP Int)
3/4
3/4
3/4
3/4
3/4
Flue Gas Temp
ºC
125
125
170
190
170
Flue Gas Volume
m
3
/h
57
67
104
126
167
Gas Injector Orifice Diameter
mm
1.60
1.70
1.85
1.78
1.78
in
0.063
0.067
0.073
0.070
0070
Flue Size (Secondary)
mm
150
150
200
200
250
in
6
6
8
8
10
Cold Water Feed Connection
R (in BSP/Exl)
11/2
11/2
11/2
11/2
11/2
Hot Water Flow Connection
R (in BSP/Exl)
11/2
11/2
11/2
11/2
11/2
*Return Connection
Rp (in BSP/Int)
3/4
3/4
3/4
3/4
3/4
Drain Port Size
R (in BSP/Ext)
3/4
3/4
3/4
3/4
3/4
Max. Working Pressure
bar
10.3
10.3
10.3
10.3
10.3
lbf/in
2
150
150
150
150
150
Max. Test Pressure
bar
20
20
20
20
20
lbf/in
2
300
300
300
300
300
Weight Empty
kg
190
200
289
294
269
lb
419
441
687
515
594
Weight Full
kg
335
488
656
618
514
lb
738
1091
1447
1135
1134
Shipping Weight
kg
199
230
316
287
293
lb
438
492
697
566
645
Shipping Dimensions Depth
mm
902
914
914
914
914
in
35 1/2 36
36
36
36
Shipping Dimensions Width
mm
768
762
762
762
762
in
30 1/4 30
30
30
30
Shipping Dimensions Height
mm
1270
1960
2210
1960
1960
in
50
77
87
77
77
ANDREWS MODEL NO.
L32/143 L65/169 L81/251
L62/309 L54/399
Propane
Butane
* If the water heater is to be
used on an unvented system,
the combined temperature/
pressure relief valve must be
fitted directly into the tank.
The secondary return is then
connected to the drain port
via a suitable tee.
Summary of Contents for L24/31
Page 3: ......
Page 5: ......
Page 14: ...INSTALLATION SECTION 3 9 Bulk Storage Vessel Installation Cylinder Installation Fig 3 ...
Page 22: ...INSTALLATION SECTION 3 17 Fig 8 Fig 8a ...
Page 24: ...INSTALLATION SECTION 3 WATER CONNECTIONS 19 Fig 10 Fig 11 ...
Page 27: ...INSTALLATION SECTION 3 WATER CONNECTIONS 22 Fig 14 Fig 15 ...
Page 30: ...INSTALLATION SECTION 3 WATER CONNECTIONS 25 Fig 18 Fig 19 ...
Page 51: ...PARTS LIST AND ILLUSTRATIONS SECTION 9 46 Hi Flo Model L32 143 Hi Flo Models L65 169 L81 251 ...
Page 53: ...PARTS LIST AND ILLUSTRATIONS SECTION 9 48 Hi Flo Models L62 309 L54 399 ...
Page 58: ...NOTES 53 ...
Page 59: ...NOTES 54 ...
Page 60: ......