LOCATION
INSTALLATION
SECTION 3
THE LAW REQUIRES THAT INSTALLATION IS CARRIED OUT BY A
PROPERLY QUALIFIED PERSON
Installations must be carried out in accordance with Gas safety (Installation and Use)
Regulations 1998, Building Regulations, The Water Supply (Water Fittings) Regulations
1999 and any requirements of the local Gas Authority, Local Authority, Water and Fire
Authorities and the current British Standards and Codes of Practice listed in Section 1.
The fittings pack supplied with the heater contains the items listed below.
1 - Installation and Service Manual.
1 - Coupler Socket
3
⁄
4
in BSP.
1 - Gas Cock.
1 - Drain Cock.
1 - Flue Adaptor Socket (Where required).
2 - Cap End 1
1
⁄
2
in BSP (Hi-Flo only).
2 - 1
1
⁄
2
in x 3in Nipples (L32/143 Model only).
1 - Warranty Card.
The draught diverter must be assembled with the legs provided.
Attach the legs to the draught diverter with the nuts and bolts provided. Fit the draught
diverter (1) as shown in Fig.1 to the water heater using the screws provided.
For Standard Range fit the draught diverter to the top of the water heater using the
location holes.
In some cases, it may be necessary to drill the fixing holes in the top cover to fit the
draught diverter to the water heater. By using the draught diverter as a template, position
carefully over the flueway and mark the hole positions to be drilled 4mm.
Fit the adaptor socket (2) and caulk into the draught diverter as shown in Fig. 1.
The location selected for installation of the heater must allow the provision of a
satisfactory flue, adequate air supply, drain facilities and must be well illuminated.
A purpose built boiler room or compartment is strongly recommended.
A manual valve for isolation of the boiler room should be installed in the gas supply;
it should be clearly identified and readily accessible for use at all times.
If a purpose built boiler room is not available, measures should be taken to protect the
heater from damage and prevent any extraneous matter from being stored on or around
the heater.
See BS 6644 Clauses 4, 5 and 6 for details.
INTRODUCTION
ASSEMBLING
THE DRAUGHT
DIVERTER
Fig. 1
Draught Diverter
Assembly
6
Top Connections
L65/169
Top Connections
L81/251 Only
Elbows must be used
Summary of Contents for L24/31
Page 3: ......
Page 5: ......
Page 14: ...INSTALLATION SECTION 3 9 Bulk Storage Vessel Installation Cylinder Installation Fig 3 ...
Page 22: ...INSTALLATION SECTION 3 17 Fig 8 Fig 8a ...
Page 24: ...INSTALLATION SECTION 3 WATER CONNECTIONS 19 Fig 10 Fig 11 ...
Page 27: ...INSTALLATION SECTION 3 WATER CONNECTIONS 22 Fig 14 Fig 15 ...
Page 30: ...INSTALLATION SECTION 3 WATER CONNECTIONS 25 Fig 18 Fig 19 ...
Page 51: ...PARTS LIST AND ILLUSTRATIONS SECTION 9 46 Hi Flo Model L32 143 Hi Flo Models L65 169 L81 251 ...
Page 53: ...PARTS LIST AND ILLUSTRATIONS SECTION 9 48 Hi Flo Models L62 309 L54 399 ...
Page 58: ...NOTES 53 ...
Page 59: ...NOTES 54 ...
Page 60: ......