44
Issue 2 14/07/16
4
Commissioning
4.4 CO² Percentage (Natural Gas)
Model Reference
Input rating
Combustion
Flue Gas Volume
Vent Temperature
kW/hr
CO
2
/CO
Cubic metres/hr
°C
EC230/600
36.6
11.0%/10 ppm
40
50 – 60
EC230/700
43.9
10.3%/20 ppm
49
50 – 60
EC230/960
58.6
9.7%/10 ppm
63
55 – 60
EC380/740
43.9
10.4%/15 ppm
49
45 – 50
EC380/980
58.6
9.8%/15 ppm
63
50 – 55
EC380/1220
73.2
10.6%/15 ppm
75
50 – 60
EC380/1400
85
11.0%/15 ppm
86
55 – 60
EC380/1900
118.7
11.0%/15 ppm
117
55 – 60
CO² Percentage (LPG)
Model Reference
Input rating
Combustion
Flue Gas Volume
Flue Temperature
kW/hr
CO
2
/CO
Cubic metres/hr
°C
EC230/600
36.6
11.2%/11.5 ppm
40
50 – 60
EC230/700
43.9
10.5%/21 ppm
49
50 – 60
EC230/960
58.6
9.9%/11.5 ppm
63
55 – 60
EC380/740
43.9
10.5%/16.5 ppm
49
45 – 50
EC380/980
58.6
9.9%/16.5 ppm
63
50 – 55
EC380/1200
73.2
10.8%/16.5 ppm
75
50 – 60
EC380/1400
85
11.2%/16.5 ppm
86
55 – 60
EC380/1900
118.7
11.2%/16.5 ppm
117
55 – 60