InfiLink 200 Installation Guide
13
Wiring the Infinet to the 9000 Controller
You connect the first piece of Infinet cabling from the 9000 controller
to the InfiLink 200. Port 1, labeled INPUT, is where the connection to
the 9000 controller, 9500, or previous InfiLink 200 comes in to the link.
(See the appropriate hardware installation guide for how to connect In-
finet at that end.)
Caution
You must have Port 1 connected to a 9000 controller, 9500, or other
InfiLink 200 to ensure proper shielding of the entire link.
The shield for Port 1 is not connected to earth ground on the board, but
the shields for Ports 2 through 5 are connected to earth ground. Port 1,
however, is wired the same way as the others, covered in the next
section.
Wiring the Infinet to the InfiLink 200
Figure 4 illustrates how to wire the Infinet cables to the removable
block terminal connectors for Ports 1 through 5 on the left side of the
InfiLink 200.
Note
You must use shielded cables for Infinet to ensure compliance with the
Class A FCC limits and to ensure reliable communications.