5
Introduction
All new Current Mode switching design offers increased power and reliability in a compact
package. Extra input and output filtering reduce EMI to extremely low levels. Reliability
features include an input fuse, thermal shutdown, current limiting, reverse battery hookup
protection and output short circuit shutdown with automatic recovery. The output voltage is
easily adjusted 1.0 volts above or below the standard output voltage. The model BCD 1000
Battery Charger supplies either 12, 24, 32 or 48 VDC from a 72, 110, 250 or 300 VDC power
source. High quality digital meters can be added (factory option) to allow monitoring of charg-
ing current and charging voltage.
Specifications
Input Voltages
Nominal (ip)
110
250
300
Actual (Vdc)
100 - 140
230 - 280
280 - 360
Input Amps (max)
14.8
6.5
5.3
Input Fuse (slow blow)
MDA-15
MDA-7
MDA-6
Output Voltages
Nominal (op)
12
24
32
48
Float (Vdc)
13.6 ± 0.05
27.2 ± 0.05
36.3 ± 0.05
54.4 ± 0.05
Absorption Voltage (Vdc)
14.4
28.8
38.4
57.6
Charging Amps
60
40
30
20
Absorption to Float
9 Amps
6 Amps
4.5 Amps
3 Amps
Battery Size (Amp Hour)*
240 – 360
160 – 240
120 – 180
80 - 120
Output Fuse (ATC)
40 x 2
40 x 2
40 x 2
25 x 2
Battery Banks
1 or 2
1 or 2
1 or 2
1 or 2
Output Adjust
± 1.0 Volts
Output Crowbar
16.0 ± 0.5 V
32.0 ± 1.0 V
43.7 ± 1.3 V
63.9 ± 2.0 V
Equalize Voltage (Vdc)
15.5
31
41.3
62
Temperature Compensation Coefficient
-30mV /
o
C
-60mV /
o
C
-80mV /
o
C
-120mV /
o
C