Installation
19
RE-DM4 and RE-DM6 RADIA Eclipse Dimmer Modules
Connecting high-voltage, single-phase input power and loads
Follow these steps to wire high-voltage (120 VAC and 240 VAC), single-phase power connections
(FIG. 16) to any of the AMX Lighting modules.
1.
Connect the green ground wire(s) to the copper ground lug on the enclosure. Ensure the ground wire
is properly connected to earth ground.
2.
Connect the white neutral wire(s) to a terminal on the enclosure's neutral terminal block. Each
terminal on the block can accept two 10 AWG wires.
3.
Provide a separate neutral wire for each dimmed zone.
4.
Connect the black line input from the electrical devices to the module's line terminal. The line input
terminal accepts a 10 AWG copper conductor.
5.
Connect load lines from the electrical devices to the Load terminals. Load 1 applies to dimmer 1,
Load 2 applies to dimmer 2, and so on.
All high-voltage connections must comply with Class 1 wiring codes.
FIG. 16
RE-DM4 and RE-DM6 (as examples only) high-voltage, single-phase power connections for line input (hot),
neutral, and ground.
Ground (green)
Ground (green)
Hot (black)
Neutral (white)
Hot (black)
Neutral (white)
to Enclosure
ground terminal
Summary of Contents for Radia RE-DM6
Page 16: ...Radia Eclipse RE DM6 Dimmer Module 10 RE DM4 and RE DM6 RADIA Eclipse Dimmer Modules ...
Page 20: ...AMX Lighting Systems 14 RE DM4 and RE DM6 RADIA Eclipse Dimmer Modules ...
Page 48: ...AMX Lighting Programming 42 RE DM4 and RE DM6 RADIA Eclipse Dimmer Modules ...
Page 102: ...Appendix C Troubleshooting 96 RE DM4 and RE DM6 RADIA Eclipse Dimmer Modules ...
Page 103: ...Appendix C Troubleshooting 97 RE DM4 and RE DM6 RADIA Eclipse Dimmer Modules ...