background image

5

5. INSTALLATION CONSIDERATIONS

LOCATION

The Well-X1

 is designed for indoor and outdoor installations. The NEMA 3R enclosure can be installed 

in direct weather. If installed outdoors, be sure the following conditions are met:

•  Do not install where ambient temperatures can drop below freezing 

or exceed 120° F.

•  Ensure  a  Tuf  Kote

  model  is  selected  (Example:  WX1-302TK) 

for  outdoor  installations.  This  proprietary  coating  is  specifically 
designed to withstand outdoor applications.

•  Use water-tight: wiring conduit, wire nuts and conduit connections 

as dictated by applicable codes and ordinances.

•  Protect the piping from mechanical damage.
•  Install the relief valve blow down tube where venting water will not 

cause personal injury or damage the surrounding property.

•  Drip  Pan  and  Drain:  To  avoid  leaking  and/or  property  damage, 

install  with  a  drip  pan  connected  to  an  adequate  working  drain 
kept clear at all times.

ORIENTATION

Ensure  the  installation  meets  all  applicable  local  codes  and  is  installed  by  a  qualified  professional. 
Additionally, the following should be noted.

•  This unit is designed for vertical installation above ground only. 

Do  not  install  horizontally  or  directly  bury  the  unit.  The  Well-
X1

 may be installed below grade in a well pit or other suitable 

enclosure.  Do  not  locate  in  an  area  where  leaking  or  flooding 
could cause property damage to surrounding areas.

•  Check codes to determine if there are any height requirements 

pertaining  to  the  Well-X1

 

Particularly,  ensure  the  bottom 

drain meets these requirements. If restrictions are imposed on 
the proximity of drain connections to the floor, the unit may be 
elevated  on  blocks  or  the  bottom  drain  tube  can  be  removed 
and plugged, after which a sampling tap may be installed in the 
water lines near the top of the Well-X1

.

Summary of Contents for WELL-X-TROL

Page 1: ...LT IN SERIOUS OR FATAL INJURY AND OR PROPERTY DAMAGE AND WILL VOID THE PRODUCT WARRANTY THIS PRODUCT MUST BE INSTALLED BY A QUALIFIED PROFESSIONAL FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND REGUL...

Page 2: ...URE TO FOLLOW INSTRUCTION MANUAL CAN CAUSE A RUPTURE OR EXPLOSION POSSIBLY CAUSING SERIOUS OR FATAL INJURY AND OR PROPERTY DAMAGE DONOTADJUSTTHEPRE CHARGEPRESSURE IF THERE HAS BEEN A REDUCTION OF THE...

Page 3: ...ontrol and tank fittings are factory installed After removing from the carton inspect the Well X1 for damage and ensure all components are present CONDUIT HOLES PUMP POWER WIRES AIR CHARGING VALVE REL...

Page 4: ...WX1 202 5 WX1 202 WX1 202 WX1 202 WX1 203 7 WX1 203 WX1 203 WX1 203 WX1 203 10 WX1 203 WX1 250 WX1 250 WX1 251 12 WX1 250 WX1 250 WX1 251 WX1 251 15 WX1 251 WX1 251 WX1 302 WX1 302 18 WX1 251 WX1 302...

Page 5: ...ing and or property damage install with a drip pan connected to an adequate working drain kept clear at all times ORIENTATION Ensure the installation meets all applicable local codes and is installed...

Page 6: ...s can cause a rupture or explosion possibly causing serious or fatal injury flooding and or property damage 2 Install the supply piping from the well pump If required install a spring loaded check val...

Page 7: ...system or into the water treatment equipment if present 6 Install a blow down tube from the relief valve to a drain or to within 6 of the floor as required by local codes A drip pan connected to an a...

Page 8: ...nting plate Attach the ground wire to the green ground screw provided Use water tight conduit connections and wire nuts for an outside application 3 Wiring is similar to a traditional mechanical press...

Page 9: ...y will read 88 to test the display illumination then a number identifying the control type i e 07 This number is for factory use and may vary by model and manufacture date 4 After a slight pause the p...

Page 10: ...ty 6 Slowly open the service valve to allow the system to pressurize The pressure may drop slightly during this process After the valve is fully open open the fixture closest to the Well X1 to begin d...

Page 11: ...ceptance is not exceeded Adjust the precharge as shown on page 12 CAUTION Exceeding Maximum Acceptance will reduce tank life and cause irreparable damage CUT OUT PRESSURE CUT IN PRESSURE 20 25 30 35 4...

Page 12: ...damage or water interruption DANGER Explosion Hazard If the Well X1 has been in service and a change to a higher pre charge is necessary due to a required change in the setting failure to follow instr...

Page 13: ...e runtime indicate an incorrect precharge undersized Well X1 or waterlogged tank Pump continues to run E2 Low Suction Pump operation below 10 psi indicates a low well level well piping leak insufficie...

Page 14: ...Check pump wiring Display will not illuminate 1 Circuit breaker or switch off 2 Faulty or loose wiring 3 Failed control 1 Check breaker and service switch 2 Check line supply wiring 3 Replace Pump wi...

Page 15: ...17 140R517 140R517 140R517 140R517 Pressure sensor tubing 6 9403R197 9403R197 9403R197 9403R197 9403R197 Pressure sensor fitting elbow 7 9401R100 9401R100 9401R100 9401R100 9401R100 Pressure sensor fi...

Page 16: ...NTIES INCLUDINGTHEIMPLIEDWARRANTIESOFMERCHANTABILITYANDFITNESSFORAPARTICULAR PURPOSE ARE SPECIFICALLY DISCLAIMED Some states do not allow limitations on how long an implied Warranty lasts so the above...

Reviews: